15
1000
1250
1500
1750
2000
2500
3000
MINIMUM - MAXIMUM OPERATING CONDITIONS
Min.-Max. Inlet Air Pressure (compressed air at inlet to dryer)
30-230 psig (2.1-16.1 kgf/cm
2
)
Max. Inlet Air Temperature (compressed air at inlet to dryer)
120°F (49°C)
Min.-Max. Ambient Temperature
Air-cooled
40°F (4°C) - 120°F (49°C)
Water-cooled
40°F (4°C) - 120°F (49°C)
REFRIGERATION SYSTEM DATA
Compressor Type
Hermetic - Non-cycling
Refrigeration Compressor Horsepower
6
7
8
10
11
13
15
BTU/HR - Refrigeration Only @ 38°F PDP & 100°F Ambient
60 HZ
60,966
67,232
75,788
97,210
100,500
130,129
150,369
50 HZ
58,591
55,802
62,904
80,684
80,750
108,007
124,805
Outlet Air Temperature (nominal at rated conditions)
85°F (29°C)
Refrigerant Type
R-404A
Refrigerant Charge
See dryer serial number tag
Suction Pressure Setting
78
Compressor Control Ranges (psig) (out-in)
High
450-348
Low
47-64
Condenser Fan Switch Setting (in-out)(psig)
Fan 1
300-230
(air-cooled models)
Fan 2
325-255
Air Flow Across Condenser (cfm) (air-cooled models)
60/50 Hz
6400/5312
6400/5312
5600/4650
5000/4150
10000/8300
10000/8300
10000/8300
Condenser Cooling Water Requirements (water-cooled models)
Recommended Water Pressure (psig)
40 min. - 120 Max*
Gallons Per Minute of Flow Required with 85°F Cooling Water
60/50 Hz
15.1/12.6
18.6/15.4
21.5/17.8
28.2/23.4
30.2/25.1
36.8/30.6
42.3/35.1
Inlet Water Connections
3/4” FPT
1” FPT
1-1/4” FPT
ELECTRICAL
Nominal Voltage
†
460/3/60
Max.- Min. voltage
506-414
Rated Load Amps**
11.50
12.10
13.60
20.70
19.20
18.59
22.44
Locked Rotor Amps**
70
86
98
130
125
150
175
Minimum Circuit Ampacity
16.73
17.42
19.30
28.17
28.44
27.53
32.41
Branch Circuit Fuse Size (amps)
25
25
30
45
45
45
50
Watts @ 35°F Evaporator & 100°F Ambient
7,850
9,223
9,777
12,621
10,823
17,607
19,693
Resistance (ohms)
2.27
1.74
1.48
1.05
1.227
0.94
0.77
Nominal Voltage
208-230/3/60***
Max. - Min. Voltage
253-187
Rated Load Amps**
22.50
25.00
27.10
35.70
41.40
39.10
48.08
Locked Rotor Amps**
156
170
195
237
239
298
380
Minimum Circuit Ampacity
32.07
35.16
37.79
48.54
59.25
56.19
67.46
Branch Circuit Fuse Size (amps)
50
60
60
80
100
90
110
Watts @ 35°F Evaporator & 100°F Ambient
7,850
9,223
9,777
12,621
10,823
17,607
19,693
Resistance (ohms)
0.56
0.44
0.38
0.26
0.306
0.21
0.19
Nominal Voltage
575/3/60
Max. - Min. Voltage
632-518
Rated Load Amps**
7.90
9.30
10.70
13.60
13.80
16.03
17.95
Locked Rotor Amps**
54
70
80
85
80
120
140
Minimum Circuit Ampacity
12.19
1379
15.54
19.16
21.63
24.19
26.60
Branch Circuit Fuse Size (amps)
20
20
25
30
35
40
40
Watts @ 35°F Evaporator & 100°F Ambient
7,850
9,223
9,777
12,621
10,823
17,607
19,693
Resistance (ohms)
3.56
2.58
2.25
1.57
2.55
1.45
1.11
Nominal Voltage
†
380-420/3/50
Max. - Min. Voltage
440-360
Rated Load Amps**
11.50
12.10
13.60
20.70
19.20
18.59
22.44
Locked Rotor Amps**
70
86
98
130
125
150
175
Minimum Circuit Ampacity
16.73
17.42
19.30
28.17
28.44
27.53
32.41
Branch Circuit Fuse Size (amps)
25
25
30
45
45
45
50
Watts @ 35°F Evaporator & 100°F Ambient
6,516
7,655
8,115
10,475
8,983
14,614
16,345
Resistance (ohms)
2.27
1.74
1.48
1.05
1.227
0.94
0.77
† For 208-230 ratings are for 230V input, for 380-420 ratings are for 400V input
** Compressor(s) only, air-cooled only
*** 230 Volt compressors are not dual frequency rated
ENGINEERING DATA
Содержание HPRP 1000
Страница 19: ...19 NOTES...