Application of pressure maintaining valve
When the difference between oil pressure and suction pressure is less than 4 bars, it may lead to
capacity-control system failure, insufficient lubrication, and serious damage to the compressor, so the
pressure maintaining valve is recommended to be installed. In addition to the installation of pressure
maintaining valve, it is also recommended to install high and low pressure difference switches. If
necessary, please contact hanbell for specific information.