6 / 156
00BNO9168-I (U0606551)
VARMAX -
Installation, Use and Maintenance
DANGER:
If you smell gas:
•
Do not use a naked flame, do not smoke, do not turn on electrical
contacts or switches.
•
Cut off the gas supply.
• Air the premises.
•
Look for the leak and repair it.
DANGER:
If you see smoke:
•
Switch off the boiler.
• Air the premises.
•
Look for the leak and repair it.
DANGER:
This boiler's earth bonding is ensured with connecting cables (green/
yellow) and specific attachment screws. During any dismantling work,
make sure you reconnect the cables concerned; it is IMPERATIVE to
reuse the original attachment screws.
1.5. Water characteristics
The following rules apply as soon as the boiler is commissioned and remain
valid until the product's end-of-life.
DANGER:
It is forbidden to use water containing glycol.
1.5.1. Preparation of the water circuit before commissioning the boiler
For all installation work (new or renovation), the water network pipes must be
meticulously cleaned. The purpose of cleaning prior to commissioning is to
remove germs and residues which are the cause of deposits.
In new installations in particular, residue from grease, oxidised metal and
even copper micro deposits must be removed.
In renovated installations, cleaning should focus on removing sludge and the
products of corrosion formed when the unit was last in operation.
There are two types of methods for cleaning and removing sludge: a high
intensity approach that takes a few hours and a slower, more gradual
approach that takes several weeks. This first type of cleaning must be done
before connecting the new boiler, and with the second type, a filter should be
installed on the back of the boiler to capture loosened deposits.
Cleaning prior to commissioning helps to improve the equipment's
performance, reduce energy consumption and fight against scaling and
corrosion. This operation must be done by a professional (water treatment).
Содержание VARMAX 120
Страница 11: ...14 09 2020 11 156 VARMAX Installation Use and Maintenance ...
Страница 44: ...44 156 00BNO9168 I U0606551 VARMAX Installation Use and Maintenance figure 33 Electrical wiring diagram ...
Страница 125: ...14 09 2020 125 156 VARMAX Installation Use and Maintenance ...
Страница 155: ...14 09 2020 155 156 VARMAX Installation Use and Maintenance ...