56 / 156
00BNO9168-I (U0606551)
VARMAX -
Installation, Use and Maintenance
figure 46 - Gas filter on VARMAX 120 and 140
figure 47 - Gas filter on VARMAX 180 to 600
WARNING:
Check gas-tightness after refitting.
screws (x4)
Gas filter
screws
(x4)
Gas filter
U0503716-#
U0503711-#
7.9.
Gas filter cleaning
- Unscrew the 4 screws that hold the gas filter in place.
- Carefully remove the gas filter.
- Clean the gas filter
ONLY
with a blower.
- Refit the filter and tighten the 4 M5 screws (tightening torque = 5 N.m).
After changing the type of gas:
- Check the gas line for leaks.
- Stick the supplied label in place of the original label.
Model
Gas
Gas flow adjustment screw presetting R1
and regulator set screw R2 / G20
CO
2
Pmax
CO
2
indicative
Pmin
180
G20
Screw R1 fully
Unscrew R1 by 2 3/4 turns, adjust R2
8,8 - 9,2
8,3 - 8,7
225
G20
Screw R1 fully
Unscrew R1 by 2 3/4 turns, adjust R2
275
G20
Screw R1 fully
Unscrew R1 by 3 turns, adjust R2
320
G20
Screw R1 fully
Unscrew R1 by 3 turns, adjust R2
390
G20
Screw R1 fully
Unscrew R1 by 4 turns, adjust R2
450
G20
Screw R1 fully
Unscrew R1 by 4 turns, adjust R2
525
G20
Screw R1 fully
Unscrew R1 by 2,5 turns, adjust R2
600
G20
Screw R1 fully
Unscrew R1 by 2,5 turns, adjust R2
Содержание VARMAX 120
Страница 11: ...14 09 2020 11 156 VARMAX Installation Use and Maintenance ...
Страница 44: ...44 156 00BNO9168 I U0606551 VARMAX Installation Use and Maintenance figure 33 Electrical wiring diagram ...
Страница 125: ...14 09 2020 125 156 VARMAX Installation Use and Maintenance ...
Страница 155: ...14 09 2020 155 156 VARMAX Installation Use and Maintenance ...