14.09.2020
27 / 156
VARMAX -
Installation, Use and Maintenance
INFORMATION:
The lengths of the ducts provided below are in linear metres (lm). The total
length of all ducts is reduced to a straight length (elbows having a straight
equivalence).
4.10.3.
On VARMAX 180 and 22
5
The type of gas is changed by replacing the
diaphragm located on the gas line.
Unscrew the 4 nuts (see opposite), then remove
the diaphragm in place (brass part).
Replace this with that provided with the boiler
(engraved B2P).
Screw the 4 nuts back in place.
Check the CO
2
After changing the type of gas:
- Check the sealing of the gas line.
- Stick the label provided in place of the
original label (G20).
Note:
In order to facilitate the operation, the mounting
flange located at the entrance to the gas line (on
the side nearest the network connection) may
require unscrewing.
4.11. Exhaust connection
Exhaust system works and national and prefectoral regulations must be
complied with.
A smoke temperature sensor guarantees the protection of exhaust ducts for
type B and C combustion products.
VARMAX boilers are approved to be connected to:
• a B23 chimney (all models)
• a B23P chimney (all models)
• a C13 air vent (models 120 to 225) except for propane gas (G31)
• a C33 air vent (models 120 to 225) except for propane gas (G31)
• a C53 air vent (all models) except for propane gas (G31)
4.11.1.
Connection to a B23 chimney
Type B23 connection:
Air from the unit's premises, extraction of gases through the roof via a flue
with natural ventilation.
WARNING:
Check that there are top and bottom ventilations in the boiler premises,
that they comply with applicable regulations and that they are not
obstructed.
figure 18 -
Diaphragm
B2P
Diaphragm
orientation
engraving
towards the
gas valve
nut (x4)
Содержание VARMAX 120
Страница 11: ...14 09 2020 11 156 VARMAX Installation Use and Maintenance ...
Страница 44: ...44 156 00BNO9168 I U0606551 VARMAX Installation Use and Maintenance figure 33 Electrical wiring diagram ...
Страница 125: ...14 09 2020 125 156 VARMAX Installation Use and Maintenance ...
Страница 155: ...14 09 2020 155 156 VARMAX Installation Use and Maintenance ...