HWC - SERIES
REV.
BUL87423
C
INSTRUCTIONS FOR
HWC
PAGE OF 9
8
Main Protective Grounding
When grounding the rack system or enclosure it is essential
that the main protective ground is connected and secured
first with its own nut before any bonding connections are
made on top. (Figure 2)
Bonding Connections
Centre Section: Attach bonding wire found in ground kit to a
centre section bonding stud, closest to the hinged side of the
enclosure, using the ring terminal and hardware provided.
Attach opposite end of wire to the nearest PET on the rear
section.
Door: Attach bonding wire to the door stud using the same
method described above. Attach the opposite end to the
nearest centre section bonding stud.
Bonding Connection
Protective Earth Ground
Figure 2
2
3
Top View
Rear Section PETs
Center Section
Bonding Studs
Door Bonding Studs