Page 133
Appendix L.
Setup file format
Any setup file loaded into a hydroSpider must be formatted correctly. This section describes these
requirements.
1.
Header
The first three lines of the file must be:
.HYDROSPIDER2
.DEV=
<device code>
.VER=
<version number>
Where
<device code>
must match the hydroSpider’s device type and
<version number>
must
match or be less than the software version currently running on the hydroSpider. If the
device code or version number is incorrect, the configuration file will be rejected.
The device codes for the various hydroSpider models are as follows:
Device Type
Device Code
hydroSpider2
40
hydroSpider2 (SDI-12 / RS-485)
41
hydroSpider2 (FlowShark / RS-232)
42
2.
Body
All setup parameters which are to be changed should be listed on separate lines. If a
parameter doesn’t need to be changed from its current value, it can be left out of the setup
file.
3.
Footer
The file must end with:
.END