Halton Max Ultra Circular (MUC) - Installation, commissioning and maintenance guide 23(31)
Version 1.0
All rights reserved © Halton
4.4
Resetting the parameters
These parameters are defined and set in the final testing in production. Changing of these
parameters should only be done by qualified person.
Enter the menu by pushing the following buttons combination: Left, Right, OK for 2s.
1.
Set
ZoffAct
parameter to the value
-150...150
.
2.
Initiate the calibration sequence start by pressing the OK button.
3.
Check if the damper blade is in a closed position.
4.
The calibration sequence is initiated.
5.
Set the
FinalK
parameter to the value
0.500...1.500
.
6.
Set the actuator parameters.
a.
Set the
ADB
parameter to the value
0..2..00%
.
b.
Set the
Dir
parameter to the value
Fwd / Rev
.
c.
Set the
ReT
parameter to the value
1...999
.
7.
Initiate a recalibration sequence by pressing the OK button.
8.
Change
Airoffset
parameter with Left / Right. buttons.
9.
Change
AuxOffset
parameter with Left / Right buttons.
10.
The software version is displayed.
11.
Controller working hours are displayed.
12.
Actuator running hours are displayed.
13.
Initiate resetting to factory settings by pressing the OK button.