![Halma Ampac EV3000 Скачать руководство пользователя страница 39](http://html1.mh-extra.com/html/halma/ampac-ev3000/ampac-ev3000_installation-and-commissioning_3353763039.webp)
MAN1813-9
35
10.7
WIP/EAID Extension Connections
The 302-6270 is the field connection board for the WIP extensions. Each board terminates sixteen
WIP and EAID extensions.
10.7.1
Connections
Field Connections Use
Field Connections
Use
TB1 - 1 ( W )
WIP No 1
TB3 - 1 ( W )
WIP No 9
TB1 - 2 ( C )
WIP / EAID Common No 1
TB3 - 2 ( C )
WIP / EAID Common No 9
TB1 - 3 ( E )
EAID No 1
TB3 - 3 ( E )
EAID No 9
TB1 - 4 ( W )
WIP No 2
TB3 - 4 ( W )
WIP No 10
TB1 - 5 ( C )
WIP / EAID Common No 2
TB3 - 5 ( C )
WIP / EAID Common No 10
TB1 - 6 ( E )
EAID No 2
TB3 - 6 ( E )
EAID No 10
TB1 - 7 ( W )
WIP No 3
TB3 - 7 ( W )
WIP No 11
TB1 - 8 ( C )
WIP / EAID Common No 3
TB3 - 8 ( C )
WIP / EAID Common No 11
TB1 - 9 ( E )
EAID No 3
TB3 - 9 ( E )
EAID No 11
TB1 - 10 ( W )
WIP No 4
TB3 - 10 ( W )
WIP No 12
TB1 - 11 ( C )
WIP / EAID Common No 4
TB3 - 11 ( C )
WIP / EAID Common No 12
TB1 - 12 ( E )
EAID No 4
TB3 - 12 ( E )
EAID No 12
TB2 - 1 ( W )
WIP No 5
TB4 - 1 ( W )
WIP No 13
TB2 - 2 ( C )
WIP / EAID Common No 5
TB4 - 2 ( C )
WIP / EAID Common No 13
TB2 - 3 ( E )
EAID No 5
TB4 - 3 ( E )
EAID No 13
TB2 - 4 ( W )
WIP No 6
TB4 - 4 ( W )
WIP No 14
TB2 - 5 ( C )
WIP / EAID Common No 6
TB4 - 5 ( C )
WIP / EAID Common No 14
TB2 - 6 ( E )
EAID No 6
TB4 - 6 ( E )
EAID No 14
TB2 - 7 ( W )
WIP No 7
TB4 - 7 ( W )
WIP No 15
TB2 - 8 ( C )
WIP / EAID Common No 7
TB4 - 8 ( C )
WIP / EAID Common No 15
TB2 - 9 ( E )
EAID No 7
TB4 - 9 ( E )
EAID No 15
TB2 - 10 ( W )
WIP No 8
TB4 - 10 ( W )
WIP No 16
TB2 - 11 ( C )
WIP / EAID Common No 8
TB4 - 11 ( C )
WIP / EAID Common No 16
TB2 - 12 ( E )
EAID No 8
TB4 - 12 ( E )
EAID No 16
NOTE:
WIP cabling is not polarity conscious.
Factory Connections
Use
CN1, CN2, CN3, CN4
Control Cable to EIS Selector boards
302 6270
LINE1
W
C
E
LINE2
LINE3
LINE4
LINE5
LINE6
LINE7
LINE8
LINE9
LINE10
LINE11
LINE12
LINE13
LINE14
LINE15
LINE16
W
C
E
W
C
E
W
C
E
W
C
E
W
C
E
W
C
E
W
C
E
W
C
E
W
C
E
W
C
E
W
C
E
W
C
E
W
C
E
W
C
E
W
C
E
W = WIP
C = Common
E = EAID
G3
G4
G2
G1
TB2
TB3
TB4
TB1
CN1
CN2
CN3
CN4
Figure 21: 302-6270 WIP Termination Board
10.7.2
Field Wiring
WIP wiring has been verified with 2kms of 0.75mm
2
with capacitance of <200nF and Inductance <
1mH.
Содержание Ampac EV3000