MAN1813-9
27
F.I.P. INPUT BOARD
INPUT
COMMON
INPUT
INPUT
INPUT
INPUT
1 6 1 5 1 4 1 3
1 2 11 1 0 9
8
7
6
5
4
3
2
1
CN1
CN2
IC41
IC40
IC39
S W 1
IC38
IC37
F 1
CN3
TB5
IC9
TB4
TB3
IC18
IC27
TB2
TB1
IC36
IC42
+
+
+
ON
1
2
3
4
5
6
7
8
750mA
RS485 IN
RS485 OUT
POWER
I N
CN4 POWER OUT
Figure 13: 302-4940 FACP Input Board
10.2
Common FACP Input Connections
Some EV3000 systems are fitted with a Common FACP input. Connection for the FACP input is
provided on a 302 5860 Line Isolation Board. The 302 4940 board is not fitted when a Common FACP
input is used.
Connections
Field Connection
TB1 - Line
FACP input
Factory Connection
TB1 - EAID
MECP EAID
(Terminated in 10KΩ if unused)
Figure 14: Common FACP Board
10.3
EWS, BGM and EIS Handset Input Connections
The BRDEV3ALM is a termination board to interconnect the EWS and EIS Audio between SECPs and
the main equipment, and provide a connection for 2 channels of BGM.
The EWS and EIS audio is monitored (configurable) and wired in a loop (redundant) configuration. If
there is a fault (short or interruption) the comms fault (see figure 2 of section 8.1) indicator will flash.
To enable the monitoring
–
turn switch 8 of the timeout selection switch ON, see section 13.2.