Halma Alicat Scientific IVCD Скачать руководство пользователя страница 18

18 

Serial Communication

Serial Communication

Connecting your device to a computer allows you to log the data that it generates. The pressure controller communicates 

digitally through its communications connector and cable using a real or virtual COM port on your computer. This section 

of the manual shows you how to operate the pressure controller using ASCII commands.

Modbus RTU Communication

For details on Modbus commands, please visit 

alicat.com/manuals

 for the Modbus operating bulletin.

Establishing Communication

After connecting your pressure controller using a communications cable, you will need to establish serial communications 

through a real or virtual COM port on your computer or programmable logic computer (PLC). 

• 

If the device is connected to a serial port, note its COM port number. This can be found in Windows® Device Manager.

• 

If you have used a USB cable to connect your device to your computer, then in most cases it will recognize your USB 

as a virtual COM port. If it does not, download the appropriate USB device driver a

alicat.com/drivers

 and note the 

COM port number as found in Windows® Device Manager.

The controller will be configured with the following settings:

•  Baud:

 19200 (by default; others can be used if the computer, its software, and the controller are all set to the same rate)

•  Data bits:

 8

•  Parity:

 none

•  Stop bits:

 1

•  Flow control:

 none

Alicat’s Serial Terminal Application

Alicat’s Serial Terminal is a preconfigured program for serial communications, functioning much like the older Windows® 

HyperTerminal. 
Download Serial Terminal for free at alicat.com/drivers. Once downloaded, simply run SerialTerminal.exe. Enter the COM 

port number to which your device is connected and the baud rate of the pressure controller. The default baud rate is 

19200, but this is adjustable by entering the 

RS-232

 

Serial

 menu on your pressure controller (

page 16

).

 ✓

 Note: 

In the following examples, 

 indicates an ASCII carriage return (decimal 13, hexadecimal D). For many devices, this 

is the same as hitting the Enter key. Serial commands are not case-sensitive.

Polling Mode

Your controller is shipped in polling mode with a unit ID of A, unless requested otherwise. Each poll returns one line of 

data every time you request it. To poll, simply enter its unit ID.

 

Poll the device:

 

[unit ID]



 Example:

 

a

  (polls unit A)

You can change the unit ID of a polling device by typing:

 

Change the unit ID:

 

[current unit ID]

@=

[desired unit ID]



 Example:

 

a@=b

  (changes unit A to unit B)

You can also do this via the device’s front panel menu (

page 16

). Valid IDs are letters A–Z, and up to 26 devices may 

be connected at a time, as long as each unit ID is unique.

Содержание Alicat Scientific IVCD

Страница 1: ...OPERATING MANUAL FOR DUAL VALVE PRESSURE CONTROLLERS Models PCD PCDS PCD3 IVCD...

Страница 2: ...ler every year Annual calibration is necessary to ensure the continued accuracy of readings and to extend the Limited Lifetime Warranty Fill out the Service Request Form at alicat com service or conta...

Страница 3: ...sure controllers for closed volumes PCDS Series anti corrosive absolute gauge and differential pressure controllers for closed volumes PCD3 Series remote sensing pressure controllers for closed volume...

Страница 4: ...PD I Control Algorithms 13 Tuning the PD PDF Control Algorithm 13 Tuning the PD I Control Algorithm 13 Troubleshooting Valve Performance with PID Tuning 14 Using a Control Deadband for Pressure Contr...

Страница 5: ...ndard dual valve pressure controller Your pressure controller s appearance and connections may differ See page 2 for more examples Backlight The monochrome display comes equipped with a backlight To t...

Страница 6: ...ode active HLD Valve hold active LCK Front display is locked POV Pressure over range of device Mounting Pressure controllers do not require straight runs of pipe upstream or downstream Most pressure c...

Страница 7: ...need Teflon tape applied to the threads Warning It is not recommended to use pipe dopes or sealants on the process connections as these compounds can cause permanent damage to the controller should th...

Страница 8: ...tween two points in the system These devices have two ports located on the front face of the unit for connection to two points in the system where the differential pressure is measured from The upstre...

Страница 9: ...nstruments with Liquids Many pressure devices may be used with chemically compatible liquids but a few warnings must be taken into account Water is about 50 times more viscous than air This is importa...

Страница 10: ...ndard 0 5 Vdc analog output signal Pin 2 is normally a constant 5 12 Vdc More pinout configuration options begin on page 24 Analog Signals Primary Analog Output Signal Most devices include a primary a...

Страница 11: ...to Tare Before every new pressure measurement cycle After significant changes in temperature or pressure After dropping or bumping the pressure controller After installing the controller in a differen...

Страница 12: ...set to Serial Front Panel the controller will accept input from either the front panel or an RS 232 RS 485 connection Neither source is a slave of the other so the controller will accept the most rec...

Страница 13: ...ow to actuate its valve s in order to achieve the commanded setpoint These settings are tuned for your specific operating conditions but changes to your process sometimes require on site adjustments t...

Страница 14: ...nd of 0 25 PSIA allows absolute pressure to vary between 29 75 and 30 25 PSIA The device will increase pressure until it reaches the setpoint of 30 PSIA With a setting of Close valve it will close bot...

Страница 15: ...Only in the serial data frame Screen and Digital Both the main display and serial data frame Device Information The ABOUT menu MENU ABOUT contains useful information for setup configuration and troub...

Страница 16: ...g and logging of all data Before connecting the pressure controller to a computer ensure that it is ready to communicate with your computer by checking the options in this menu For more on how to issu...

Страница 17: ...isplay Screen Lighting The options and wording in the screen lighting menu will vary for monochrome versus color displays On monochrome displays press LESS CONTRAST or MORE CONTRAST to adjust the cont...

Страница 18: ...others can be used if the computer its software and the controller are all set to the same rate Data bits 8 Parity none Stop bits 1 Flow control none Alicat s Serial Terminal Application Alicat s Ser...

Страница 19: ...eads zero Taring an absolute pressure sensor requires a barometer and aligns the absolute pressure sensor with the external barometric pressure For an accurate tare a gauge or absolute pressure sensor...

Страница 20: ...us sign New setpoint unit ID s floating point number setpoint Example as 15 00 setpoint of 15 00 PSIG Quick Command Guide Note Serial commands are not case sensitive In these examples the unit ID of t...

Страница 21: ...sure standard you know is accurate If it checks out keep using it but tell us about the drop at your next annual recalibration so we can check it out for you Issue How can I see pressure in different...

Страница 22: ...Unit ID to make sure you are addressing it properly with your serial commands 3 Check the pinout common pinouts are listed starting on page 24 4 Make sure the COM number matches the one your software...

Страница 23: ...rrD Torr mmHgA mmHgG mmHgD Millimeter of mercury at 0 C inHgA inHgG inHgD Inch of mercury at 0 C mmH OA mmH OG mmH OD Millimeter of water at 4 C NIST conventional mmH OA mmH OG mmH OD Millimeter of wa...

Страница 24: ...ptional 1 5 Vdc or 0 10 Vdc output signal 7 Power In 8 Ground common for power digital communications analog signals and alarms Caution Do not connect power to pins 1 through 6 as permanent damage can...

Страница 25: ...og Out Analog Out Analog Out RX or A Analog Out NC Analog Out 3 Ground Analog In NC NC NC NC NC 4 NC Ground NC NC NC Analog Out NC 5 Power In Ground Power In Ground Ground Power In Ground 6 NC Ground...

Страница 26: ...nalog Setpoint Input Analog Setpoint Input 5 Serial RS 232 TX signal Optional RS 485 B Serial RS 232 TX Signal Optional RS 485 B 6 Static 5 12 Vdc Optional Secondary analog output 4 20 mA 0 5 Vdc 1 5...

Страница 27: ...2021 05 26 REV 1 DUAL VALVE PRESSURE CONTROLLER OPERATING MANUAL 27...

Страница 28: ...d Plot No A 147 Road No 24 Next to Spraytech Circle opp Metropolitan Company Wagle Industrial Estate Thane West Mah r shtra 400 604 91 022 41248010 China SE Asia info cn alicat com alicat com cn 2nd F...

Отзывы: