Preventive Maintenance
62
Silencer Series Booster Pump
p/n: 029-0020-83-0
A pump must be able to pump FULL capacity at 150 PSI, 70% capacity at 200
PSI and 50% capacity at 250 PSI.
Tank-to-Pump Flow Rate Test
Note: This procedure is provided as a reference only. It does not supersede any
local procedures.
1.
Fill the water tank until it overflows.
2.
Close the tank fill line, bypass the cooling line, and all the pump intakes.
3.
Attach sufficient hose lines and nozzles to pump the desired discharge rate.
4.
With the pump in gear, open the discharge to which the hose is attached
and begin pumping water.
5.
Increase the engine throttle until the maximum consistent pressure is
obtained on the discharge gauge.
6.
Close the discharge valve without changing the throttle setting. Refill the
tank through the top fill opening or a direct tank line. The bypass valve may
be opened during this time to prevent pump overheating.
7.
Reopen the discharge valve, and check the flow through the nozzle using a
Pitot tube or flow meter. Adjust the engine throttle to bring the pressure to
the amount previously determined.
8.
Compare the flow rate measured to the NFPA minimum or the designed
rate of the pump. If the flow rate is lower, a problem exists in the tank-to-
pump line. The minimum flow rate should be continuously discharged until
80% of the tank is discharged.
9.
The pump should not experience mechanical problems, power loss, or
overheat during the test.
Performance Testing Equipment and Materials
Pumpers should be tested from draft at not over a 10’ (3 meters) lift with 20’ (6
meters) of suction hose. Pumpers rated at 1,500 GPM and above often require
two separate 20-foot lengths of suction hose and a lower lift height.
Use smooth bore test nozzles of accurate size with the pitot gauge. The vol-
ume pumped is then determined by reference to discharge tables for smooth
nozzles. Preferably, nozzles will be used on a Siamese deluge gun for greatest
Содержание Silencer APS Series
Страница 6: ...Overview 6 Silencer Series Booster Pump p n 029 0020 83 0...
Страница 22: ...Introduction 22 Section 2 Introduction Hale Products Inc May 2006 Rev B...
Страница 32: ...Accessories Options 32 Section 2a Accessories Hale Products Inc May 2006 Rev B...
Страница 66: ...Preventive Maintenance 66 Silencer Series Booster Pump p n 029 0020 83 0...