5
20. FANUC PLC
5-113
Co
nne
20. FANUC PLC
Available PLCs
Communication Setting
The recommended communication parameter settings of the PLC and the V7 series is as follows:
Available Memory
The available memory setting range varies depending on the PLC model. Be sure to set within the
range available with the PLC to be used. Use [TYPE] when assigning the indirect memory for macro
programs.
Select PLC Type
PLC
Unit/Port
Connection
Power Mate
Power Mate-Model H/D
Port on the CPU
unit (JD14)
RS-422
[Wiring Diagram 2]
Power Mate i Model
H/D
JD42
RS-232C [Wiring Diagram 1]
JD40
RS-422
[Wiring Diagram 3]
Item
Setting on PLC
V7 Comm. Parameter Setting
Baud rate
19200 bps (fixed)
−
Port
0 (fixed)
−
Parity
Even (fixed)
−
Transmission code
Data length
8 (fixed)
−
Stop bit
1 (fixed)
−
Memory
TYPE
Remarks
D
(data table)
0
X
(input relay)
1
WX as word device
Y
(output relay)
2
WY as word device
R
(internal relay)
3
WR as word device
K
(keep relay)
4
WK as word device
T
(timer)
5
C
(counter)
6