5-82
12. GE Fanuc PLC
12. GE Fanuc PLC
Available PLCs
Communication Setting
The recommended communication parameter settings of the PLC and the V7 series is as
follows:
90 Series
90 Series SNP-X
Select PLC Type
PLC
Unit/Port
Connection
90 series
Series 90-30
Programmable
coprocessor (PCM)
RS-232C
[Wiring Diagram 1]
RS-485
[Wiring Diagram 2]
90 series
(SNP-X)
Series 90 micro
Series 90-30
CPU port
RS-485
[Wiring Diagram 3]
Item
Setting on PLC
V7 Comm. Parameter Setting
Baud rate
19200 bps
19200 bps
Port
01 (“0” for
×
10, “1”
×
1)
1
Parity
Odd
Odd
Transmission code
Data length
8
8
Stop bit
1
1
Functions
Host link function (fixed)
−
Response delay time
0 (fixed)
−
Timeout
None (fixed)
−
ASCII/HEX
HEX (fixed)
−
Item
Setting on PLC
V7 Comm. Parameter Setting
Baud rate
19200 bps
19200 bps
Parity
Odd
Odd
Transmission code
Data length
8
8
Stop bit
1
1
Functions
SNP-X (fixed)
−
Содержание Monitouch V7
Страница 1: ...V7...
Страница 3: ......
Страница 17: ......
Страница 57: ......
Страница 95: ...2 38 3 Errors Displayed on the V7 Series Please use this page freely...
Страница 97: ......
Страница 150: ...1 Ethernet 2 FL net OPCN 2 3 MELSECNET 10 4 CC Link 5 OPCN 1 6 T LINK 7 PROFIBUS DP Network Communications...
Страница 151: ......
Страница 207: ......
Страница 343: ...5 136 29 Automationdirect PLC Please use this page freely...