YASKAWA PLC
Available PLCs
* Other PLCs can also be connected with Memobus.
Communication Setting
The recommended communication parameter settings of the PLC and the V7 series is as follows:
Memobus
Select [TYPE 1] or [TYPE 2] for [Trans. Mode] in the [Comm. Parameter] dialog of the
V-SFT editor.
Select PLC Type
PLC
Unit/Port
Connection
memobus
GL60 series
JAMSC-IF60
JAMSC-IF61
JAMSC-IF611
RS-232C
[Wiring Diagram 1]
JAMSC-IF612
JAMSC-IF613
RS-422
[Wiring Diagram 5]
GL120, GL130 series
Memobus port on the
CPU module
RS-232C
[Wiring Diagram 1]
JAMSC-120NOM27100
RS-422
[Wiring Diagram 6]
PROGIC-8
PORT2 on the CPU unit
RS-232C
[Wiring Diagram 2]
CP9200SH/MP900
CP9200SH
CP-217IF
RS-232C
[Wiring Diagram 3]
[Wiring Diagram 4]
RS-422
[Wiring Diagram 7]
MP920
MP930
Memobus port on the
CPU module
RS-232C
[Wiring Diagram 1]
217IF
RS-232C
[Wiring Diagram 3]
RS-422
[Wiring Diagram 8]
Item
Setting on PLC
V7 Comm. Parameter Setting
Baud rate
19200 bps
19200 bps
Port
1
1
Parity
Even
Even
Transmission code
Data length
8-bit RTU (fixed)
−
Stop bit
1
1
Error check
CRC (fixed)
−
Port delay timer
0 (fixed)
−
PLC Model
V7 Setting
Contents
GL60 series, PROGIC-8
TYPE 1
Special binary code
GL120/130 series
TYPE 2
Standard binary code
Содержание Monitouch V7
Страница 1: ...V7...
Страница 3: ......
Страница 17: ......
Страница 57: ......
Страница 95: ...2 38 3 Errors Displayed on the V7 Series Please use this page freely...
Страница 97: ......
Страница 150: ...1 Ethernet 2 FL net OPCN 2 3 MELSECNET 10 4 CC Link 5 OPCN 1 6 T LINK 7 PROFIBUS DP Network Communications...
Страница 151: ......
Страница 207: ......
Страница 343: ...5 136 29 Automationdirect PLC Please use this page freely...