5
5. MATSUSHITA PLC
5-41
Co
nne
5.
MATSUSHITA PLC
Available PLCs
Communication Setting
The recommended communication parameter settings of the PLC and the V7 series is as follows:
* If a tool port (the ladder port for RS-232C) is used, the range of PLC parameter setting is
limited as below. Adjust the PLC parameter setting to communication parameter setting of
the V7 series.
Baud rate:
9600, 19200bps (115 kbps available with FP2)
Parity:
Odd (fixed)
Data bit:
8 (or 7, select “8” normally)
Stop bit:
1 (fixed)
Select PLC Type
PLC
Unit/Port
Connection
MEWNET
FP1
RS-232C port on the CPU unit
RS-232C
[Wiring Diagram 1]
FP3
AFP3462
RS-232C
[Wiring Diagram 1]
AFP3463
RS-422
[Wiring Diagram 4]
FP5
AFP5462
RS-232C
[Wiring Diagram 1]
FP10
RS-232C tool port on the CPU unit
RS-232C
[Wiring Diagram 1]
AFP5462
RS-232C
[Wiring Diagram 1]
FP10S
RS-232C port on the CPU unit
RS-232C
[Wiring Diagram 1]
AFP3462
RS-232C
[Wiring Diagram 1]
AFP3463
RS-422
[Wiring Diagram 4]
FP0
RS-232C tool port on the CPU unit
MATSUSHITA’s RS-232C cable
AFC8513
RS-232C port on the CPU unit
RS-232C
[Wiring Diagram 3]
FP2
RS-232C tool port on the CPU unit
MATSUSHITA’s RS-232C cable
AFC8513
RS-232C port on the CPU unit
RS-232C
[Wiring Diagram 2]
Item
Setting on PLC
V7 Comm. Parameter Setting
Baud rate
19200 bps
19200 bps
Port
[0]
×
10, [1]
×
1
1
Parity
Even
Even
Transmission code
Data bit
7 (ASCII)
7
Stop bit
1
1
Transmission mode
Computer link function (fixed)
−
Control signal
Invalid (fixed)
−
Содержание Monitouch V7
Страница 1: ...V7...
Страница 3: ......
Страница 17: ......
Страница 57: ......
Страница 95: ...2 38 3 Errors Displayed on the V7 Series Please use this page freely...
Страница 97: ......
Страница 150: ...1 Ethernet 2 FL net OPCN 2 3 MELSECNET 10 4 CC Link 5 OPCN 1 6 T LINK 7 PROFIBUS DP Network Communications...
Страница 151: ......
Страница 207: ......
Страница 343: ...5 136 29 Automationdirect PLC Please use this page freely...