5
3. SHARP PLC
5-31
Co
nne
JW Series: Link Unit Switch Setting
Baud Rate: 19200 bps
JW100/70H COM Port, JW20 COM Port:
System Memory Setting
The settings for communications with the V7 series should be made at the system memory as shown
below.
•
JW-70CU/100CU, JW70CUH/100CUH, JW22CU
•
JW-32CUH/33CUH
- Communication port 1
- Communication port 2
Switch
Setting
Contents
SW0
4
Command mode
SW1
1
Station address (lower half)
SW2
0
Station address (upper half)
SW3-1
OFF
Not used
SW3-2
ON
4-wire system
SW3-3
OFF
Not used
SW3-4
ON
Even parity
SW4
0
Baud rate
0: 19200
1: 9600
2: 4800
3: 2400
4: 1200
5: 600
SW7
ON
Terminating resistance provided
System Memory
Setting
Contents
#236
30H
Stop bit: 2 bits, parity: even, baud rate: 192000
#237
01H
Port
System Memory
Setting
Contents
#234
30H
Stop bit: 2 bits, parity: even, baud rate: 192000
#235
01H
Port
System Memory
Setting
Contents
#236
30H
Stop bit: 2 bits, parity: even, baud rate: 192000
#237
01H
Port