28
TROUBLE SHOOTING
Electricity
leakage of
temperature
controller
1. The service time is too long.
2. The environment is too dirty.
3. Humidity is too high.
1. Change temperature controller.
2. Use brush to remove dust.
3. Make the temperature dry and
control the environment humidity.
Temperature
controller
out of order
1.
There is leakage of
temperature sensing medium.
2. Damage of cam of contacting
point spring, etc.
Change temperature controller.
The probe of
temperature
sensing tube
doesn’t
contact
evaporator
well
It has not been mounted to
position or changed during
transportation.
Mount it again.
One
compartmen
t doesn’t
cool
1.Check the
electromagnetism
valve connection cord if it is
broken or doesn’t connect well
2.Check the main control panel if it
is out of order
3. the
electromagnetism
valve
has
broken down .
1.Connect the connection cord
2.Replace the main control panel
3.Replace the electromagnetism
valve.