Functions and control

5.1 main functions and control specifications 

Including brief introduction to air conditioners of series models and electric control function.

5.1.1 Automatic running

5.1.1.1 Single cold automatic run mode:

After entering into this mode, the main control “MCU” determines the corresponding work pattern

according to the indoor temperature so as to maintain the preset temperature (the preset temperature is 26

).

When the indoor temperature is below 26

, outlet air from compressor is off,

the automatic wind from fan

motor is low, and wind can be set to high, medium or low by hand. When the indoor temperature is or above

26

, the unit enters the cooling mode and conducts the cooling programme (the preset temperature is 26

),

outlet air from compressor is on and indoor fan motor run in fixed wind speed.

5.1.1.2 Automatic running mode

When the running mode is turned to automation after starting the system, the system will first determine

the running mode according to the current room temperature and then will run according to the determined

mode. Tr in the following selection conditions means room temperature, Ts means setting temperature, Tp

means temperature of indoor coil pipe

a. Tr 23

         

running cooling mode

b. Tr<23

    

running heating mode   

  

After turning to the automation mode, the running mode can be switched between cooling mode, fan

mode and heating mode according to the change of the indoor ambient temperature. But the automatic

conversion between cooling mode and heating mode must be conducted after 15 minutes.

5.1.2 Indoor temperature control

Temperature control range : 16

—30

Temperature control precision: 1

Compressor can’t be controlled by temperature sensor within 2 minutes after it starts

5.1.2.1 Cooling mode:

When Tr> Ts, outdoor fan motor and compressor on, and indoor fan motor run at fixed wind speed. When Tr

Ts, outdoor fan motor and compressor off, and when Tr > Ts, outdoor fan motor and compressor are working

again .If Tr=Ts, the indoor fan motor , outdoor fan motor and the compressor’s state will not change.

5.1.2.2 Heating mode:

When Tr

Ts, compressor, four-ways valve and outdoor fan motor is on, indoor fan

motor runs as in cold blast avoidance mode, and 4

of compensation is added after compressor is started.

When Tr>Ts+5

, compressor is off, and the indoor fan motor runs as in cold blast avoidance mode.

When Tr<Ts+5

, compressor, four-ways valve and outdoor fan motor is on, and the indoor fan motor runs

as in the mode of avoiding cold blast.

5.1.3 Cooling run mode:

temperature control range :16

—30

temperature control precision: 1

compressor can’t be controlled by temperature sensor within 2 minutes after it starts.

control character: when Tr

Ts, outlet air from compressor is on and indoor fan motor run at fixed

wind speed. When Tr Ts, outlet air from compressor is off , and when Tr > Ts, outlet air from compressor

is on.

Functions and Control

HSU-18 24 HEK13/R2

10

Содержание HSU18XH7-G - Ductless Split Indoor Wall Mount Unit Heat...

Страница 1: ...l individuals of potential dangers in attempting to service a product Products powered by electricity should be serviced or repaired only by experienced professional technicians Any attempt to service...

Страница 2: ...tions and control 10 5 1 Main functions and control specification 10 5 2 Value of thermistor 15 6 System configuration 23 6 1 System configuration 23 6 2 Instruction 24 7 Service diagnosis 31 7 1 Caut...

Страница 3: ...ols for quick cleaning of the inside of the air conditioner Anti mold filter Catches most small particles and remove unpleasant odors effectively Sleep mode The setting temprature and the indoor noise...

Страница 4: ...ling the equipment for a repair Working on the equipment that is connected to a power supply can cause an electrical shook If it is necessary to supply power to the equipment to conduct the repair or...

Страница 5: ...lder in an enclosed room can cause oxygen deficiency 2 1 2 Cautions Regarding Products after Repair Warning Be sure to use parts listed in the service parts list of the applicable model and appropriat...

Страница 6: ...n the refrigerant system If air enters the refrigerating system an excessively high pressure results causing equipment damage and injury If the refrigerant gas leaks be sure to locate the leak and rep...

Страница 7: ...can cause oxygen deficiency 2 1 3 Cautions Regarding Products after Repair Warning Be sure to use parts listed in the service parts list of the applicable model and appropriate tools to conduct repair...

Страница 8: ...but may nevertheless be valuable to the reader such as tips and tricks Caution Caution A caution is used when there is danger that the reader through incorrect manipulation may damage equipment loose...

Страница 9: ...P 1 3 3 59 1 16 7 8 15 5 32X12 19 32X10 9 32 8 6 9 3 0 11 0 11 48 9 16X15 9 32X14 11 32 HSU 18 24HEK13 R2 7 5 27 18000 3 5 7 8 1640 10 98 11 28 11 26 4 6 17 7 625 8 pints hr BTU h w 1 4 1 2 5 8 3 8 5...

Страница 10: ...4 19 6 691 9 26 7 19 4 23 9 5m 3413 1480 1 1 5 4 Rotary Compressor Rotary Compressor 50A452P ASH218RN R410A Axial fan 42 7 8X17 5 16X36 13 16 37 5 16X13 3 8X33 1 16 35 NMOC Ze Gles RB68EP or equivalen...

Страница 11: ...ansformer input 2 CN2 connector for terminal block 3 CN3 connector for transformer output 4 CN5 or CN5 1 connector for up and down step motor 5 CN6 connector for ambient temp sensor and piping temp 6...

Страница 12: ...en cooling mode fan mode and heating mode according to the change of the indoor ambient temperature But the automatic conversion between cooling mode and heating mode must be conducted after 15 minute...

Страница 13: ...JK WHPSHUDWXUH H SLUDWLRQ SUHYHQWLRQ KHQ WKH WHPS RI FRLO SLSH LV DERYH FRPSUHVVRU DQG RXWOHW DLU VWRS UXQQLQJ VHFRQGV ODWHU DQG LQOHW DLU UXQV DV WKH WHPS VHQVRU LV RII KHQ FRPSUHVVRU VWDQGV E IRU PL...

Страница 14: ...WKH ZD YDOYH VWDUWV UXQQLJ VHFRQGV HDUOLHU WKDQ FRPSUHVVRU GRHV IWHU FRPSUHVVRU VWRSV UXQQLJ WKH ZD YDOYH FRQWLQXHV UXQQLQJ IRU PLQXWHV DQG WKHQ VWRSV I FKDQJLQJ WKH XQLW IURP KHDWLQJ WR FRROLQJ WKH Z...

Страница 15: ...RYHU PLQXWHV LQ WRWDO DQG RYHU PLQXWHV FRQWLQXRXVO DQG WKH WHPS RI LQGRRU FRLO SLSH LV EHORZ RPSUHVVRU UXQV PLQXWHV FRQWLQXRXVO DQG WKH WHPS RI LQGRRU FRLO SLSH GHFUHDVHV SHU PLQXWHV DQG WKLV RSHUDWLR...

Страница 16: ...1 7 Sleep function the timer indicator lights up 5 1 7 1 In cooling defrosting mode the temp setting increases 1 one hour later after start up After another hour the temp setting increase by more 1 a...

Страница 17: ...n is available If the buzzer rings 2 times the the auto recovery function of power on is unavailable If there is no EEPROM the unit is taken off the off function of the memory function of power down B...

Страница 18: ...3062 62 1807 58 2405 1 24 1 19 6 62 7992 58 9853 55 3351 1 22 1 17 7 59 4984 55 9729 52 5917 1 20 1 15 8 56 3905 53 1320 50 0006 1 17 1 13 9 53 4631 50 4521 47 5523 1 15 1 11 10 50 7048 47 9230 45 238...

Страница 19: ...7 1 68 1 60 50 8 2713 7 7345 7 2237 1 73 1 64 51 7 9531 7 4280 6 9291 1 77 1 68 52 7 6489 7 1353 6 6480 1 81 1 72 53 7 3580 6 8556 6 3797 1 85 1 76 54 7 0796 6 5884 6 1237 1 90 1 79 55 6 8131 6 3329 5...

Страница 20: ...3603 3 91 3 52 96 1 6643 1 4810 1 3163 3 97 3 56 97 1 6138 1 4347 1 2739 4 02 3 61 98 1 5650 1 3900 1 2331 4 08 3 66 99 1 5180 1 3470 1 1937 4 13 3 70 100 1 4726 1 3054 1 1559 4 19 3 75 101 1 4287 1...

Страница 21: ...3 58 9863 1 66 1 54 14 66 3463 61 0123 56 0565 1 64 1 52 13 62 8755 57 9110 53 2905 1 62 1 51 12 59 6076 54 9866 50 6781 1 60 1 49 11 56 5296 52 2278 48 2099 1 58 1 47 10 53 6294 49 6244 45 8771 1 56...

Страница 22: ...5496 0 84 0 83 29 8 7942 8 4964 8 2013 0 87 0 86 30 8 4583 8 1621 7 8691 0 91 0 90 31 8 1371 7 8428 7 5522 0 95 0 93 32 7 8299 7 5377 7 2498 0 98 0 97 33 7 5359 7 2461 6 9611 1 02 1 00 34 7 2546 6 96...

Страница 23: ...3 1 7064 1 5697 2 78 2 58 75 1 7974 1 6533 1 5194 2 83 2 63 76 1 7434 1 6021 1 4710 2 88 2 67 77 1 6913 1 5528 1 4243 2 92 2 71 78 1 6409 1 5051 1 3794 2 97 2 75 79 1 5923 1 4592 1 3360 3 02 2 80 80 1...

Страница 24: ...0 6482 0 5792 4 51 4 07 108 0 7059 0 6308 0 5632 4 57 4 12 109 0 6877 0 6140 0 5478 4 63 4 16 110 0 6700 0 5977 0 5328 4 69 4 21 111 0 6528 0 5820 0 5183 4 74 4 26 112 0 6361 0 5667 0 5043 4 80 4 31 1...

Страница 25: ...method of using it In order to meet this expectation of the users giving sufficient explanations taking enough time can be said to reduce about 80 of the requests for servicing However good the insta...

Страница 26: ...ull display or unclear display during operation indicates the ries have been used up Please change batteries If the remote controller can t run normally during operation reload several minutes later b...

Страница 27: ...tical flap Pos 1 Pos 2 Pos 3 Pos 4 Pos 5 Auto swing 1 Status display of air flow When restart after remote turning off the remote memorize the previous Move the vertical blade by a knob on air to adju...

Страница 28: ...her 1 hours temp rises by 1 futher The unit will run for further 6 hours then stops Temp is higher than temp setting so that room temperature won t be too low for your sleep 1 hours after SLEEP mode s...

Страница 29: ...fore the setting of healthy airflow function Notice Do not direct the flap by hand Otherwise the grille will run incorrectly If the grille is not run correctly stop for a minute and then start adjusti...

Страница 30: ...rifying filter face outside and the black side face the unit The green side of the bacteria killing medium air and the white side face the unit Please keep the bacteria killing medium air purifying fi...

Страница 31: ...yourself Do not use for the purpose of storage of food art work precise equipment breeding or cultivation CAUTION Take fresh air occasionally especially when gas appliance is running at the same time...

Страница 32: ...asily reached 5 The wiring method should be in line with the local wiring standard 4 The distance between the indoor unit and the floor should be more than 2m 3 If the fuse on PC board is broken pleas...

Страница 33: ...operates Check the indoor PCB Check to make sure that the indoor PCB is broken Equipment operates but does not cool or does not heat only for heat pump Diagnosis by service port pressure and operating...

Страница 34: ...sure to turn off power switch before connect or disconnect connector or else parts damage may be occurred E1 Room temperature sensor failure CN6 E2 Heat exchange sensor failure CN6 NO Check the value...

Страница 35: ...95 5286 5279 5231 5216 5134 5095 5315 5329 5318 5310 5297 5251 5247 5159 5102 5270 5351 5340 5324 5316 5283 5266 5230 5190 5362 5353 5348 5321 5296 5280 5248 5225 5418 5372 5361 5354 5329 5315 5286 52...

Страница 36: ...6315 6310 6305 6410 6460 6450 6447 6420 6417 6410 6408 6405 6450 6528 6495 6484 6462 6458 6450 6436 6421 6570 6536 518 6476 6460 6454 6445 6430 6630 6620 6600 6553 6524 6500 6470 6462 6442 6470 6431...

Страница 37: ...5 5 7 6 15 20 25 o indoor temp humidity 46 heating capacity and indoor outdoor temp table HSU 18HEK13 R2performance curves 5120 5036 4970 5230 5167 5036 5317 5245 5102 5270 5135 5631 5579 5346 5745 56...

Страница 38: ...oor temp DB WB 15 20 25 15 o 5 5 7 6 15 20 25 o indoor temp humidity 46 heating capacity and indoor outdoor temp table HSU 24HEK13 R2performance curves 1 2 3 4 5 6 7 conoling capacity w outdoor tempe...

Страница 39: ...22 32 23 32 24 outdoor temp humidity 46 power consumption value temp table HSU 18HEK13 R2 performance curves Power consumption temp curves 1 8 1 2 1 8 1 4 2 0 1 5 2 2 1 6 2 5 1 8 2 6 7 1 9 4 3 0 2 2...

Страница 40: ...1862 1921 1694 1725 1764 1782 1835 1881 1925 1962 1765 1796 1823 1867 1905 1923 1985 2039 1912 1934 1965 1989 2010 2035 2078 2162 1956 1968 1989 2006 2035 2074 2126 2185 2013 2067 2095 2115 2137 2165...

Страница 41: ...68 5...

Страница 42: ...68 5...

Страница 43: ...8 5 Sound level HSU 18HEK13 R2 HSU 18HEK13 R2 pressure M L 47 44 40 56 220V 60HZ HSU 18 24HEK13 R2 9...

Страница 44: ...HSU 24HEK13 R2 49 46 43 58 pressure M L HSU 24HEK13 R2 9...

Страница 45: ...oller on a wall place where the indoor unit can receive signals when the uorescent lamps in the room are lightened Outdoor Unit Place which is less affected by rain or direct sunlight and is suf cient...

Страница 46: ...the dent of heat insulation materials of indoor unit 2 Insert the indoor outdoor electric cable from backside of indoor unit and pull it out on the front side then connect them 3 Coat the aring seal f...

Страница 47: ...refrigerant pipes and indoor unit using a vacuum pump then Spanner Forced fastening without careful centering may damage the threads and cause a leakage of gas Pipe Diameter Fastening torque Liquid s...

Страница 48: ...h leakage breaker 4 Flare pipe Lean Damage of are Crack Partial Too outside t c e r r o c n I t c e r r o C On Drainage It becomes high midway The gap with the ground is too smal There is the bad smel...

Страница 49: ...Domestic air conditioner Piping diagrams 68 5...

Страница 50: ...Indoor 48 HSU 18 24HEK13 R2...

Страница 51: ...OR 2 There are no dotted lines on cool only type marked with Wire is connected from 4 marked with on terminal block to 1 TO INDOOR FRESH AIR MOTOR 4 way valve CAPACITOR CAPACITOR 1 See above for wirin...

Страница 52: ...3 4 CN6 B4B XH 5V C16 0 1UF R17 4 7K R37 10K 12V R36 1K E2 4 7uF 16V E3 4 7uF 16V R40 1K R SRCK RCK SER COM3 COM2 R25 560 R27 560 1 CON7 1 CON8 GND 5V A B C D CT 50HZ PGO WF ST FLZ YJ HEAT R101 1K R10...

Страница 53: ...Dimensional drawings 10 4 Dimensional drawings HSU 18HEK13 R2 HSU HEK13 R2 HSU 18 24HEK13 R2 51...

Страница 54: ...Dimensional drawings HSU 24HEK13 R2 340 948 840 9 52mm 3 8 HSU 18HEK13 R2 860 760 9 52mm 3 8 HSU 18 24HEK13 R2 52 820 308 908...

Страница 55: ...HSU HEK13 R2 Indoor unit 10 5 Center of gravity 795 265 190 320 115 89 780 540 302 126 245 350 HSU 07 09 12HEK13 R2 Outdoor unit HSU 18 24HEK13 R2 53...

Страница 56: ...HSU 24HEK13 R2 Indoor unit 938 265 190 377 115 89 HSU 18 24HEK13 R2 54...

Страница 57: ...40 43 n w o d l l u p 0 3 20 18 10 0 16 23 32 10 20 30 indoor temp WB Notes The graphs are based on the following condition Equivalent piping length 7 5m Level difference 0m h g i h e t a r w o l f r...

Страница 58: ...10 7 Accessories R 03 dry battery 2 6 Plastic cap 4 Cover 1 4 Pipe supporting plate 1 Drain elbow 0 Steel nail Cushion HSU 18 24HEK13 R2 HSU 18 24HEK13 R2 57...

Страница 59: ...e power supply is 220 230V 50Hz D means the developing sequence and R1 means the refrigerant is R407C Applicable frequency 1 60HZ Applicable voltage 13 220 230V Heating Apparance of indoor unit is EKs...

Страница 60: ...Liu Ming He Shiquan Wu Hongjin Zhang Jing The end 0532 8893 6935 HSU 18 24HEK13 R2...

Отзывы: