Fixing of outdoor unit

Indoor Unit

Selection of Installation Place

Power Source

Selection of pipe

Outdoor Unit

Fix the unit to concrete or block with bolts(   10mm) and nuts firmly and horizontally.

When fitting the unit to wall surface, roof or rooftop, fix a supporter surely with nails
or wires in consideration of earthquake and strong wind.

If vibration may affect the house, fix the unit by attaching a vibration-proof mat.

Place, robust not causing vibration, where the body can be supported
sufficiently.
Place, not affected by heat or steam generated in the vicinity, where
inlet and outlet of the unit are not disturbed.
Place, possible to drain easily, where piping can be connected with the
outdoor unit.
Place, where cold air can be spread in a room entirely.
Place, nearby a power receptacle, with enough space around. (Refer
to drawings).
Place where the distance of more than lm from televisions, radios,
wireless apparatuses and fluorescent lamps can be left.
In the case of fixing the remote controller on a wall, place where the
indoor unit can receive signals when the fluorescent lamps in the room
are lightened.

Place, which is less affected by rain or direct sunlight and is
sufficiently ventilated.
Place, possible to bear the unit, where vibration and noise are
not increased.
Place, where discharged wind and noise do not cause a
nuisance to the neighbors.
Place, where a distance marked       is available as illustrated
in the above figure.

Before inserting power plug into receptacle, check the voltage without fail. The power source is the same as the corresponding name plate.

Install an exclusive branch circuit of the power.

A receptacle shall be set up in a distance where the power cable can be reached. Do not extend the cable by cutting it.

To this unit, both liquid and gas pipes shall be insulated

as they become Iow temperature in operation.

Use optional parts for piping set or pipes covered with

equivalent insulation material.

The thickness of the pipe must be 0.8 mm at least.

Liquid pipe(     )

Gas pipe(     )

2

6.35mm(1/4")

9.52mm(3/8")

Floor fixing dimensions
of the outdoor unit
(Unit:mm)

6.35mm(1/4")

12.7mm(1/2")

For 09

For 12

140

500

140

256

Содержание HSU-09H03/R

Страница 1: ...te controller R 03 dry battery Mounting plate Drain hose Steel nail cement Screw Plastic cap Drain elbow Cover Cushion 1 1 2 3 4 5 6 7 8 9 2 1 1 6 4 1 1 4 Number of articles Accessory parts 4X50 4X25 more than 5cm more than 10cm more than 60cm more than 15cm more than 10cm more than 10cm more than 10cm Attention must be paid to the rising up of drain hose G F A Drawing for the installation of indo...

Страница 2: ...ase of fixing the remote controller on a wall place where the indoor unit can receive signals when the fluorescent lamps in the room are lightened Place which is less affected by rain or direct sunlight and is sufficiently ventilated Place possible to bear the unit where vibration and noise are not increased Place where discharged wind and noise do not cause a nuisance to the neighbors Place where...

Страница 3: ...ounting plate is first fixed for the position of wall hole Fix to side bar and lintel a mounting bar Which is separately sold and then fasten the plate to the fixed mounting bar Make a hole of 66 mm in diameter slightly descending to outside the wall Install piping hole cover and seal it off with putty after installation Section of wall hole Piping hole pipe Outdoor side Thickness of wall Indoor s...

Страница 4: ...e pipe has already existed 2 Pull out the cable on the front side and connect the cable making a loop 1 Insert the drain hose into the dent of heat insulation materials of indoor unit 2 Insert the indoor outdoor electric cable from backside of indoor unit and pull it out on the front side then connect them 3 Coat the flaring seal face with refrigerant oil and connect pipes Cover the connection par...

Страница 5: ...gure 3 BRN WHT BLK RED YEL GRN BRN WHT BLK RED YEL GRN Indoor unit Outdoor unit HSU 09H03 R QXF HSU 12H03 R QXF HSU 09H03 R DB HSU 12H03 R DB HSU 09C03 R DB HSU 12C03 R DB YEL GRN YEL GRN Indoor unit Outdoor unit RED RED BLK BLK WHT WHT Two ways for the installation of indoor part as illustrated Way One When the pipes go from the back of the indoor unit you can connect the fresh air tube with the ...

Страница 6: ...inal block and insert the plugs fully into terminal block then tighten the screws If wiring is not correct proper operation can not be carried out and controller may be damaged If the drain elbow is used please attach it as figure Note Only for heat pump unit Drawing for the installation of indoor and outdoor units Insert the cable according to terminal number in the same manner as the indoor unit...

Страница 7: ...s using specified torque 5 Tighten the caps on the valves with specified torque Valve rod Valve cap 7 9 20 25 Tighten torque N m When connecting pipe exceeds 5 meters 16g refrigerant shall be added per exceeding meter Charge according to the following list Piping length Additional amount 5m 7m 10m No need 32g During this procedure 50g refrigerant will be discharged in piping This must be strictly ...

Страница 8: ...n pan of the indoor unit and confirm that drainage is carried out surely to outdoor In case that the attached drain hose is in a room please apply heat insulation to it without fail Please kindly explain to our customers how to operate through the instruction manual Gas leak from pipe connecting Heat insulation of pipe connecting Are the connecting wirings of indoor and outdoor firmly inserted to ...

Отзывы: