background image

Outdoor unit

6.Purging Method:To use vacuum pump

Detach the service port's cap of 3-way valve, the

valve rod's cap for 2-way valve and 3-way's, connect

the service port into the projection of charge hose

(Iow) for gaugemanifold. Then connect the projection

of charge hose (center) for gaugemanifold into

vacuum pump.

3-way valve
Gas Side

2-way valve

2-way valve

Service port cap

Gaugemanifold(for R410A)

Vacuum pump(for R410A)

Open

Close

Liquid Side

Open the handle at Iow in gaugemanifold, operate

vacuum pump. If the scale-moves of gause (Iow)

reach vacuum condition in a moment, check         again.

Vacuumize for over 15min. And check the level gauge

which should read -0.1 MPa (-76 cm Hg) at Iow

pressure side. After the completion of vacuumizing,

close the handle 'Lo' in gaugemanifold and stop the

operation of the vacuum pump.

Check the condition of the scale and hold it for 1-2min.

If the scale-moves back in spite of tightening, make

flaring work again, the return to the beginning of         .

Open the valve rod for the 2-way valve to an angle of

anticlockwise 90 degrees.

After 6 seconds, close the 2-way valve and make

the inspection of gas leakage.

No gas leakage?

In case of gas leakage, tighten

parts of pipe connection. If

leakage stops, then proceed

steps.

Detach the charge hose from the service port, open

2-way valve and 3-way. Turn the valve rod anticlockwise

until hitting lightly.

To prevent the gas leakage, turn the service port's

cap, the valve rod's cap for 2-way valve and 3-way's

a little more than the point where the torque increases

suddenly.

After attaching the each caps, check the gas leakage

around the caps.

CAUTION:

1.If the refrigerant of the air conditioner leaks, it is necessary to

 discharge all the refrigerant. Vacuumize first, then charge the liquid

 refrigerant into air conditioner according to the amount marked on

 the name plate.

2.Please do not let other cooling medium, except specified one (R410A),

  or air enter into the cooling circulation system. Otherwise, there will be

 abnormal high pressure in the system to make it crack and lead to

  personal injuries.

If it does not stop gas leakage, discharge
whole refrigerants from the service port.
After flaring work again and vacuumize,
fill up prescribed refrigerant from the gas
cylinder.

Anti countercurrent joint

3-way valve

2-way valve

7

6

6

6

1

2

3

1

3

4

5

6

7

8

7

3-way valve

2-way valve

3-way valve

2-way valve

3-way valve

2-way valve

HSU-09HV03/R2(DB)
HSU-12HV03/R2(DB)

HSU-07HV03/R2(DB)

HSU-18HV03/R2(DB)

HSU-22HV03/R2(DB)

HSU-12HVB03/R2(DB)

HSU-22HVA103/R2(DB)

HSU-18HVA103/R2(DB)

HSU-09HVA103/R2(DB)
HSU-12HVA103/R2(DB)

HSU-07HVA103/R2(DB)

Tube(for R410A)

3-way valve

Valve rod cap

Valve rod cap

7

7

Open

90

O

Содержание HSU-07HVA103

Страница 1: ...e 9 Nipper 12 Reamer 10 Gas leakage detector or soap and water solution 11 Measuring tape Explain sufficiently the operating means to the user according to this manual A G G F A C D E No Accessory par...

Страница 2: ...ated Place possible to bear the unit where vibration and noise are not increased Place where discharged wind and noise do not cause a nuisance to the neighbors Place where a distance marked is availab...

Страница 3: ...article When the mounting plate is first fixed for the position of wall hole Fix to side bar and lintel a mounting bar Which is separately sold and then fasten the plate to the fixed mounting bar Make...

Страница 4: ...the underside and then put it down perpendicularly Remove terminal cover at right bottom corner of indoor unit then take off wiring cover by removing its screws When connecting the cable after instal...

Страница 5: ...e cable from the back side of the unit then pull it out on the front side Loosen the screws and insert the cable ends fully into terminal block then tighten the screws Pull the cable slightly to make...

Страница 6: ...neer Before adding additional refrigerant perform air purging from the refrigerant pipes and indoor unit using a vacuum pump then charge additional refrigerant Use the same method on indoor unit Loose...

Страница 7: ...steps Detach the charge hose from the service port open 2 way valve and 3 way Turn the valve rod anticlockwise until hitting lightly To prevent the gas leakage turn the service port s cap the valve ro...

Страница 8: ...ried out Please install the drain hose so as to be downward slope without fail Please don t do the drainage as shown below Please pour water in the drain pan of the indoor unit and confirm that draina...

Отзывы: