background image

Open

No gas leakage?

5.

Detach the charge hose

6.

from the service port, open 2-way valve and 3-way. Turn

the valve rod anticlockwise until hitting lightly.

In case of gas leakage, tighten parts of pipe connection. If

leakage stops, then proceed 6. steps

If it does not stop gas leakage, discharge whole refrigerants from the service

port. After flaring work again and vacuumize, fill up prescribed

refrigerant from the gas cylinder.

Anti countercurrent joint

Gaugemanifold(for R410A)

2-way valve Liquid Side

3-way valve Gas Side

Vacuum pump(for R410A)

Tube(for R410A)

Close

2-way valve

3-way valve

Open 90

O

2-way valve

3-way valve

2-way valve 3-way valve

2-way valve

3-way valve

Valve rod cap

Valve rod cap

Service port cap

To prevent the gas leakage, turn the service port’s cap, the valve rod’s cap for 2-way

valve and 3-way’s a little more than the point where the torque increases suddenly.

After attaching the each caps, check the gas leakage around the caps.

7.

8.

Step 1.

Step 2.

Step 3.

Step 7.

Step 6.

Step 4.

The power source must be exclusively used for air

ƽ

conditioner. (Over I0A)

In the case of installing an air conditioner in a moist place,

ƽ

please install an ea-

For installation in other places, use a circuit breaker as far

ƽ

as possible.

Pipe cutting is carried out with  a  pipe cutter and burs must

ƽ

be removed.

After inserting the flare nut, flaring work is carried out.

ƽ

If the refrigerant of the air conditioner leaks, it is necessary to discharge all the

ƽ

refrigerant. Vacuumize first, then charge the liquid refrigerant into air conditio-
ner according to the amount marked on the name plate.

Please do not let other cooling medium, except specified one (R410A), or air

ƽ

enter into the cooling circulation system. Otherwise, there will be abnormal
high pressure in the system to make it crack and lead to personal injuries.

Power Source Installation

Cutting and Flaring Work of Piping

Flare tooling die

1.Cut pipe

2.Remove burs

3.Insert the flare nut

CAUTION

Flare tool for R410A

Conventional flare tool

Clutch-type

clutch-type(Rigid-type) Wing-nut type (Imperial-type)

A

0~0.5mm

1.0~1.5mm

1.5~2.0mm

rth leakage breaker.

4.Flare pipe

Lean

Damage of flare Crack

Partial

Too outside

Correct

Incorrect

On Drainage

It becomes

high midway.

The gap with the

ground is too small.

There is the bad
smell from a ditch

It waves.

The end is imm-
ersed in water.

Please install the drain hose so as to be downward slope without fail.
Please don’t do the drainage as shown below.

ƽ
ƽ

Please pour water in the drain pan of the indoor unit, and confirm that drainage

ƽ

is carried out surely to outdoor.

In case that the attached drain hose is in a room, please

ƽ

apply heat insulation to

Less than

5cm

it without fail.

4

Check Items for Test Run

in boxes

Gas leak from pipe connecting?

Heat insulation of pipe connecting?

Are the connecting wirings of indoor and outdoor firmly

Is the connecting wiring of indoor and outdoor firmly fixed?

Is drainage securely carried out?

Is the earth line securely connected?

Is the indoor unit securely fixed?
Is power source voltage abided by the code?

Is there any noise?

Is the lamp normally lighting?
Are cooling and heating (when in heat pump) performed normally?

Is the operation of room temperature regulator normal?

Please kindly explain to our customers how to operate
through the instruction manual.

Check for Installation and Test Run

Ƶ

inserted to the terminal block?

Ƶ

1

1+2=

kg

R410A

2

kg

2=

1=

B

C

D

F

E

kg

A

This product contains fluorinated greenhouse gases covered by 
the Kyoto Protocol. Do not vent into the atmosphere.
Refrigerant type:R410A
GWP* value:1975
GWP=global warming potential
Please fill in with indelible ink,
• 1      the factory refrigerant charge of the product
• 2      the additional refrigerant amount charged in the field and
• 1+2  the total refrigerant charge
on the refrigerant charge label supplied with the product.
The filled out label must be adhered in the proximity of the product
charging port (e.g. onto the inside of the stop value cover).
A  contains fluorinated greenhouse gases covered by the Kyoto 
Protocol
B  factory refrigerant charge of the product: see unit name plate
C   additional refrigerant amount charged in the field
D   total refrigerant charge
E   outdoor unit
F   refrigerant cylinder and manifold for charging 

Contains fluorinated greenhouse gases
covered by the Kyoto Protocol

Refrigerant charge label

Ƶ

Put check mark

 

Содержание HSM18HEA03/R2

Страница 1: ...age without fail The power source is the same as the corresponding name plate Install an exclusive branch circuit of the power A receptacle shall be set up in a distance where the power cable can be r...

Страница 2: ...out on the front side then connect them 3 Coat the aring seal face with refrigerant oil and connect pipes Cover the connection part with heat insulation materials closely and make sure xing with adhe...

Страница 3: ...A 4G0 75mm2 3 2 POWER 1 N L C 3 2 1 N L C HSM18HEA03 R2 DB HUM18HA03 R2 DB HSM18HRA03 R2 DB HUM18HA03 R2 DB HSM18HEK03 R2 DB HUM18HB03 R2 DB Power cable 3G2 5mm2 Outdoor unit Indoor unit A B Outdoor...

Страница 4: ...5mm 1 5 2 0mm rth leakage breaker 4 Flare pipe Lean Damage of are Crack Partial Too outside Correct Incorrect On Drainage It becomes high midway The gap with the ground is too small There is the bad...

Страница 5: ...suficientemente ventilado Elija un lugar que permita soportar el peso de la unidad y que no amplifique el ruido y las vibraciones Seleccione un lugar en el que los residuos y el viento generado por la...

Страница 6: ...la entubaci n del refrigerante utilizando cinta protectora Entubaci n en otra direcci n Corte con una cuchilla la cubierta de entubaci n de acuerdo con la direcci n de entubaci n y doble los tubos de...

Страница 7: ...e los tapones completamente en los mismos Apriete entonces los tornillos Inserte el cable de acuerdo con el n mero del terminal de la misma forma que hizo con la unidad interior Si el cableado no es c...

Страница 8: ...nadero regulados por el Protocolo de Kioto No los libere libremente a la atm sfera Tipo de refrigerante R410A Valor GWP 1975 GWP Potencial de contribuci n al calentamiento global Escriba con tinta ind...

Страница 9: ...alla luce diretta del sole e che sia sufficientemente ventilato Luogo in grado di sostenere il peso dell unit dove le vibrazioni ed il rumore non siano aumentati Luogo dove l aria di scarico ed il rum...

Страница 10: ...ono essere uniti alla tubatura refrigerante usando nastro protettivo Tubature con altre direzioni Tagliare con le tenaglie il coperchio per la tubazione in base alla direzione della stessa e piegarla...

Страница 11: ...ntare le viti ed inserire completamente le spine nel blocco terminali poi stringere le viti Inserire il cavo in base la numero del terminale allo stesso modo usato per l unit interna Se il cablaggio n...

Страница 12: ...o valvola a stelo Coperchio porta di servizio Fase 2 Fase 3 Fase 6 Fase 4 Fase 7 12 Installare il tubo di scarico in modo che sia inclinato correttamente verso il basso Non installare lo scarico come...

Страница 13: ...ne soit pas expos la pluie ou la lumi re du jour et qui soit suffisamment ventil S lectionnez un emplacement capable de supporter l unit o les vibrations et le bruit n augmentent pas S lectionnez un...

Страница 14: ...ion thermique et fixez avec du ruban adh sif Le c ble des unit s int rieures ext rieures et le tuyau de vidange doivent tre fix s au tuyau de r frig rant avec un ruban protecteur Tuyauterie dans une a...

Страница 15: ...t ins rez totalement les fiches dans le bornier puis resserrez les vis Ins rez le c ble selon le num ro de la borne tel que pour l unit int rieure Si le c blage est incorrect le fonctionnement sera in...

Страница 16: ...ype de r frig rant R410A Valeur de GWP 1975 GWP global warming potential potentiel de r chauffement de la plan te Merci de remplir l encre ind l bile 1 La charge de r frig rant usine de l appareil 2 l...

Отзывы: