507769-05G / 31-5000656
Page 18 of 55
Issue 2223
Maximum Allowable Intake or Exhaust Vent Length in Feet
Concentric Termination at Elevation 0 - 2,000 ft
Number of 90°
Elbows Used
1-1/2” Pipe
2” Pipe
2-1/2" Pipe
3" Pipe
Capacity
Capacity
Capacity
Capacity
045
070
090
045
070
090
045
070
090
045
070
090
1
10
10
n/a
53
38
22
90
70
39
111
111
104
2
n/a
n/a
48
33
17
85
65
34
106
106
99
3
43
28
12
80
60
29
101
101
94
4
38
23
n/a
75
55
24
96
96
89
5
33
18
70
50
19
91
91
84
6
28
13
65
45
14
86
86
79
7
23
60
40
9
81
81
74
8
18
55
35
n/a
76
76
69
9
13
50
30
71
71
64
10
n/a
45
25
66
66
59
NOTE - Size intake and exhaust pipe length separately. Values in table are for Intake OR Exhaust, not combined total. Both Intake
and Exhaust must be same pipe size.
NOTE - Additional vent pipe and elbows used to terminate the vent pipe outside the structure must be included in the total vent length
calculation.
Table 7C.
Maximum Allowable Intake or Exhaust Vent Length in Feet
Concentric Termination at Elevation 2,001 - 10,000 ft
Number of 90°
Elbows Used
2” Pipe
2-1/2" Pipe
3" Pipe
Capacity
Capacity
Capacity
045
070
090
030/
045
070
090
030/
045
070
090
1
35
25
15
90
63
39
111
111
104
2
30
20
10
85
58
34
106
106
99
3
25
15
n/a
80
53
29
101
101
94
4
20
10
75
48
24
96
96
89
5
15
n/a
70
43
19
91
91
84
6
10
65
38
14
86
86
79
7
n/a
60
33
9
81
81
74
8
55
28
n/a
76
76
69
9
50
23
71
71
64
10
45
18
66
66
59
NOTE - Size intake and exhaust pipe length separately. Values in table are for Intake OR Exhaust, not combined total. Both Intake
and Exhaust must be same pipe size.
NOTE - Additional vent pipe and elbows used to terminate the vent pipe outside the structure must be included in the total vent length
calculation.
Table 7D.