– 62 –
13. Disconnect the yellow hose attached to the
sealed system.
14. Run the recovery pump to achieve a vacuum
(see
Recovery Procedures
, in this section
of the service guide). Then, run a purge on
the recovery pump (see
Self Purge/Auto
Evacuate
, in this section of the service guide).
Carefully disconnect all hoses.
NOTE
: The system should now be fully charged
and ready for operation. To be certain, complete
the following check list:
1. Double check the sealed system valve and
the sealed system for leaks.
2. Secure the cap on the charge valve.
3. Check the system for proper operation.
4. Complete all of the EHS Safety requirements.
Purging Non-Condensable Gasses from
the Recovery Cylinder
1. Allow the recovery cylinder to sit undisturbed
for 24-hours to allow the air to rise to the top.
2. Determine the ambient temperature in the
room.
3. Connect the high-pressure manifold gauge
to the vapor port of the recovery cylinder and
compare the pressure reading to the ambient
temperature.
4. If the pressure reading is higher than the
pressure listed for the ambient temperature,
slowly open the manifold to release the non-
condensable gas until the pressure reading
is within 5 psi of the corresponding chart
pressure.
5. Close vapor port and allow the recovery
cylinder to sit for 10-minutes; then check the
cylinder pressure again.
6. Repeat the process if necessary.
Relative Refrigerant Pressures (psi)
Temp.
in °F
Freon
®
R-22
Suva
®
R-410A
Suva
®
R-134a
Temp.
in °C
32 °F
57.7
101
28.0
0 °C
34 °F
60.4
105
29.7
1.1 °C
36 °F
63.1
109
31.5
2 °C
38 °F
65.9
114
33.4
3.3 °C
40 °F
68.7
118
35.3
4.4 °C
42 °F
71.7
123
37.3
5.6 °C
44 °F
74.7
127
39.3
6.7 °C
46 °F
77.8
132
41.4
7.8°C
48 °F
81.0
137
43.5
8.9°C
50 °F
84.2
142
45.7
10.0°C
55 °F
92.7
156
51.5
12.8 °C
60 °F
102
170
57.7
15.6 °C
65 °F
111
185
64.3
18.3 °C
70 °F
122
200
71.3
21.1 °C
75 °F
132
217
78.9
23.9 °C
80 °F
144
235
86.9
26.7 °C
85 °F
156
254
95.4
29.4 °C
90 °F
168
274
104
32.2 °C
95 °F
182
295
114
35.0 °C
100 °F
196
317
124
37.8 °C
Model
R410a (oz.)
AZ95H09DACK1
34 oz.
AZ95H09EACK1
34 oz.
AZ95H12DACK1
38.45 oz.
AZ95H12EACK1
38.45 oz.
AZ95H18DACK1
48 oz.
AZ95H09EACK1
50 oz.
Refrigerant Charge