45
FlexFit Pro
5. Installation
ENGLISH
SE
C
TION D
High ESP Duct Product Information
The High ESP Duct Indoor Air Handler ships consisting of a
single assembly. The High ESP Duct indoor unit is operated
via a factory supplied wired remote control.
that are located at all four corners of the High ESP Duct
The High ESP Duct unit receives 230 volt line voltage
from a connection at the outdoor condensing unit.
There is no requirement for independent line voltage
connections.
The High ESP Duct unit has a built-in condensate pump and
Duct unit. This hose connects the High ESP Duct
condensate drain outlet to the building’s condensate
drain system.
Included with the High ESP Duct unit is factory provided
insulating tape. This tape should be placed over the
refrigerant piping connections at the indoor unit to prevent
sweating.
Built-in
Condensate
Pump and
Float Switch
Indoor
AM24LP2VHA
AM36LP2VHA
AM48LP2VHA
Rated Cooling Capacity Btu/hr
24,000
35,000
47,000
Rated Heating Capacity Btu/hr
26,500
37,500
52,000
Voltage, Cycle, Phase V/Hz/-
208/230/60/1
208/230/60/1
208/230/60/1
Fan Speed Stages
4+Auto
4+Auto
4+Auto
Air
fl
ow (Turbo/ High/
Med/Low/Quiet) CFM
845/670/530/470
1100/950/735/675
1350/1150/930/765
Motor Speed (Turbo/ High/
Med/Low/Quiet) RPM
950/860/760/700
1000/920/860/810
1180/1080/1010/960
Max. External Static Pressure in.W.G
(Pa)
0.6(150)
0.6(150)
0.6(150)
Indoor Sound Level dB (Turbo/High/
Med/Low)
38/35/32/29
32/28/25/23
41/36/33/31
Dimension: Height in (mm)
9 7/8 (250)
9 7/8 (250)
9 7/8 (250)
Dimension: Width in (mm)
37 5/8 (957)
59 (1500)
59 (1500)
Dimension: Depth in (mm)
25 3/4 (655)
28 3/8 (720)
28 3/8 (720)
Weight (Ship/Net)- lbs (kg)
81.1/68.8(36.8/31.2)
130.1/121.3 (59/55)
132.3/114.6 (60/52)
Connections
Flare
Flare
Flare
Liquid O.D. in
3/8
3/8
3/8
Suction O.D. in
5/8
5/8
5/8
Drainpipe Size O.D. in
1 1/4
1 1/4
1 1/4
Internal Condensate Pump
Standard
Standard
Standard
Max. Drain-Lift height in(mm)
27 9/16(700)
27 9/16(700)
27 9/16 (700)
Introduction - Overview
YR-E17 Wired Controller
See Section E for more information
assembly.
High ESP
The High ESP Duct unit will install above the ceiling or in a soffit
Содержание FlexFit Pro AL24LP2VHA
Страница 1: ...SYJS 04 2017REV B Edition 2017 04 FlexFit PRO ...
Страница 8: ...FlexFit Pro 6 ...
Страница 9: ......
Страница 10: ...AW24LP2VHA AW36LP2VHA ...
Страница 11: ......
Страница 12: ...10 ...
Страница 13: ...11 ...
Страница 14: ...12 ...
Страница 15: ...13 ...
Страница 16: ...14 ...
Страница 17: ...15 ...
Страница 18: ...16 ...
Страница 19: ...17 ...
Страница 20: ...18 ...
Страница 37: ...35 FlexFit Pro ...
Страница 53: ...49 FlexFit Pro Part 5 Outdoor Units 50 2 Dimensions 53 3 Piping 55 4 Wiring diagrams 55 5 Installation 58 ...
Страница 72: ...68 FlexFit Pro 3 Outdoor PCB PCB 0151800054B Power module 0150401824 ...
Страница 90: ...86 FlexFit Pro Fig 4 1 ...
Страница 91: ...87 FlexFit Pro Fig 4 2 ...
Страница 108: ...104 FlexFit Pro 7 Controller External View of Remote Controller 7 1 Remote Controller YR HBS01 ...
Страница 121: ...Haier Commercial Air Condition Web Http www haier com Haier reserves the right to make change without any notice ...