11.1.
2 For the unit with new wired controller YR-E12 (0010451521)
Remote
control
indoor
PCB flash
times
Wired
controller
display
Central
controller
display
Fault description
Possible cause
Remedy
Purpose
Items to be checked
10
08(08H)
21D
Fault in drain system
Float switch is disconnected
25min or longer.
Restorable when
given corrective
signal.
To prevent condensate
spilling out of drain
pan
Water line, water pump, float
switch, I/O voltage
1
01(01H)
01D
Fault in indoor ambient
temperature sensor
Sensor is open-circuit or
short-circuit for 2min or longer.
Restorable when
given corrective
signal.
To test input signal of
system.
Hardware connection, I/O
voltage division
2
02(02H)
02D
Fault in indoor coil
temperature sensor
Sensor is open-circuit or
short-circuit for 2min or longer.
Restorable when
given corrective
signal.
To test input signal of
system.
Hardware connection, I/O
voltage division
3
74(4AH)
11D
Fault in outdoor ambient
temperature sensor
Sensor is open-circuit or
short-circuit for 2min or longer.
Restorable when
given corrective
signal.
To test input signal of
system.
Hardware connection, I/O
voltage division
Fault in outdoor coil
temperature sensor
Sensor is open-circuit or
short-circuit for 2min or longer.
Restorable when
given corrective
signal.
To test input signal of
system.
Hardware connection, I/O
voltage division
4 73(49H)
12D
Fault in discharging
temperature sensor
Sensor is open-circuit or
short-circuit for 2min or longer.
Restorable when
given corrective
signal.
To test input signal of
system.
Hardware connection, I/O
voltage division
Overcurrent
Detected CT current is above
the limit three times within
30min.
Restorable after
repair.
To prevent overload
(electric parameter).
Power supply, wiring,
compressor, pressure
5 72(48H)
10D
Power failure
Wrong phase, phase failure or
phase loss.
Restorable after
repair.
To ensure power
supply.
Wiring, control board, power
supply
Fault with high pressure
Low
pressure
switch
is
activated three times within
30min.
Restorable after
repair.
To prevent overload
(pressure parameter).
Wiring, circuit, pressure switch,
refrigeration system
6 83(53H)
14D
Fault with low pressure
Low
pressure
switch
is
activated.
Restorable after
repair.
To prevent refrigerant
leak.
Wiring, circuit, pressure switch,
refrigeration system
8 07(07H)
06D
Communication
error
between wired controller
and indoor unit
Communication error lasts
4min or longer.
Restorable when
given corrective
signal.
To ensure
transmission to and
from control board.
Wiring circuit, transmission
voltage
9 06(06H)
05D
Communication
error
between indoor and
outdoor units
Communication error lasts
4min or longer.
Restorable when
given corrective
signal.
To ensure
transmission to and
from control board.
Wiring circuit, transmission
voltage
11
11(0BH)
30D
External alarm signal input
External signal is cut out for
10s or longer.
Restorable when
given corrective
signal.
To control external
connection provided
for building.
External signal, wiring, control
board
>a__WcU[S^ <[c >a`V[e[a`Wc
-293
-
Содержание AB092ACBHA
Страница 47: ... a__WcU S c a V e a Wc AU88NATBEA 66 33 1 23 4 43 33 61 2 3 160 2 15 3 52 47 ...
Страница 235: ... N2 4 C N344 C J eab d VW bc eWV V SYcS_ a__WcU S c a V e a Wc 235 ...
Страница 236: ... a__WcU S c a V e a Wc N2 4 C N344 C J Taeea_ d VW bc eWV V SYcS_ 236 ...
Страница 238: ... N364 A D N3 4 A E J eab d VW bc eWV V SYcS_ a__WcU S c a V e a Wc 238 ...
Страница 239: ... N364 A D N3 4 A E J Taeea_ d VW bc eWV V SYcS_ a__WcU S c a V e a Wc 239 ...
Страница 241: ... N464 C D J eab d VW bc eWV V SYcS_ a__WcU S c a V e a Wc 241 ...
Страница 242: ... N464 C D J Taeea_ d VW bc eWV V SYcS_ a__WcU S c a V e a Wc 242 ...
Страница 244: ... N364 A N3 4 A J eab d VW bc eWV V SYcS_ a__WcU S c a V e a Wc 244 ...
Страница 245: ... N364 A N3 4 A J Taeea_ d VW bc eWV V SYcS_ a__WcU S c a V e a Wc 245 ...
Страница 247: ... a__WcU S c a V e a Wc AU242AHBEA AU282AHBEA PCB top side printed diagram 247 ...
Страница 248: ... a__WcU S c a V e a Wc AU242AHBEA AU282AHBEA PCB bottom side printed diagram 248 ...
Страница 250: ... a__WcU S c a V e a Wc AU28NAHBEA AU36NAIBEA AU42NAIBEA PCB top side printed diagram 250 ...
Страница 251: ... a__WcU S c a V e a Wc AU28NAHBEA AU36NAIBEA AU42NAIBEA PCB bottom side printed diagram 251 ...
Страница 253: ... a__WcU S c a V e a Wc AU52NAIBEA PCB top side printed diagram 253 ...
Страница 254: ... a__WcU S c a V e a Wc AU52NAIBEA PCB bottom side printed diagram 254 ...
Страница 256: ... a__WcU S c a V e a Wc AU88NATBEA PCB top side printed diagram 256 ...
Страница 257: ... a__WcU S c a V e a Wc AU88NATBEA PCB bottom side printed diagram 257 ...
Страница 272: ... a__WcU S c a V e a Wc Indoor units except for AP18 AP88 PCB printed diagram 272 ...
Страница 278: ... a__WcU S c a V e a Wc Cabinet indoor units PCB circuit diagram 278 ...
Страница 279: ... a__WcU S c a V e a Wc Cabinet indoor units PCB printed diagram 279 ...
Страница 343: ... a__WcU S c a V e a Wc 14 Air volume and external static pressure curves 343 ...
Страница 349: ...1 8 0 2 4 25 27 22 5 5 heating air discharge angle 45 Temperature distribution a__WcU S c a V e a Wc 349 ...
Страница 357: ...1 8 0 2 4 25 27 22 5 5 heating air discharge angle 45 Temperature distribution a__WcU S c a V e a Wc 357 ...
Страница 364: ...MEMO Commercial Air Conditioner ...