Condition for the PCB data:
1.Working ambient temperature:
-
10
℃~
70
℃
, relative humidity:30%
~
95%
2.Preserved ambient temperature:
-
20
℃~
80
℃,
relative humidity
:
30%
~
95%
3.Power supply:220VAC
、
50/60Hz
,
voltage range:160V
~
250V
4.Precise of temperature control:
±
1
℃
P
ort and definition
P1
——
connect to external power supply, live line: L (220VAC)
P2
——
connect to external power supply, neutral line: N (0VAC)
P3
、
4
、
5
、
6
——
control external load, neutral line: N1
、
N2
、
N3
、
N4(0VAC)
P7
——
control external load, electrical heat: HEAT (control output 220VAC)
P8
——
control external load, health function: OXYGEN (control output 220VAC)
P9
——
control external load, humidification: HUMI (control output 220VAC)
P10
——
control external load, SWING(control output 220VAC)
P11
——
control external load, WATER PUMP(control output 220VAC)
P12
——
control external load, indoor fan motor low speed: L(control output 220VAC)
P13
——
control external load, indoor fan motor mid speed: M(control output 220VAC)
P14
——
control external load, indoor fan motor high speed: H(control output 220VAC)
P15
——
communication with fixed frequency single outdoor unit: COMM(0~220VAC)
P16
——
input control, signal live line: L’(220VAC)
P17
——
input control, signal neutral line: N’(0VAC)
CN1
——
input port of transformer (220VAC)
CN2
——
input port 1 of transformer (no use)
CN3
——
input port 2 of transformer (no use)
CN4
——
input port 3 of transformer (1-2
、
14VAC
,
3-4
、
12VAC)
CN5
——
input control, connecting port to wired controller: CONTROLLER
(
three bits: 1. power supply:
12VAC, 2. power supply: 0VAC, 3. communication: COMM.
)
.
CN6
——
input control, ambient temp.-coil temp. sensor connecting port: ROOM/PIPE
(
1-2
、
ROOM
,
3-4
、
PIPE
。)
Indoor ambient temp. sensor: R25=23K
Ω
+-2.5%
,
B25/50=4200K+-3%
,
range:
(
-40
,
80
)
Indoor coil temp. sensor: R25=10K
Ω
+-3%
,
B25/50=3700K+-3%
,
range:
(
-20
,
90
)
CN7
——
control external load, fresh air control: FRESH
(
1. blank, 2. power supply 0VDC, 3. control
output: 12VDC.
)
CN8
——
input signal: FREEZE
(
no use
)
CN9
——
input control
(
no use
)
CN10
——
communication with fixed frequency single outdoor unit: (0~12VDC)
CN11
——
input signal, door switch: DOOR
(
1-2 short circuit is normal, cut off P8 output
)
CN12
——
input signal, external alarm input: ALARM
(
1-3 short circuit is normal, if cut off, air
conditioner stops work.
)
Note: For convertible type, cassette type, duct type units, CN11 and CN12 must be in short
circuit, or PCB will display failure information.
CN13
——
input signal, wiring port of remote receiver board: RECEIVE BOARD
(
1. power supply 5VDC,
2. power supply 0VDC, 3. remote signal, 4. signal output of running lamp 0VDC, 5. signal output of timer
AB, AE, AD units PCB ports function:
-145-
Содержание AB072XCBAA
Страница 21: ... a__WcU S c a V e a Wc AU84NXTBAA 66 33 1 23 4 43 33 61 2 3 160 2 15 3 52 21 ...
Страница 28: ... a__WcU S c a V e a Wc w y z x wt9 61 xt 98 96 816 yt5861 zt256 1 o MRWMHI p t9 61 2v xB r 2v xB r 2wzxB 28 ...
Страница 138: ... a__WcU S c a V e a Wc AU282XHBAA AU422XIBAA PCB printed diagram 138 ...
Страница 141: ... a__WcU S c a V e a Wc AU84NXTBAA PCB printed diagram 141 ...
Страница 144: ... a__WcU S c a V e a Wc AB AE AD units PCB printed diagram 144 ...
Страница 149: ... a__WcU S c a V e a Wc AF07 142XCBAA PCB printed diagram 149 ...
Страница 180: ...MEMO Commercial Air Conditioner ...