10.4.12 High work-intense protection
Outdoor display LED1 flash 21 times
Method of High work-intense control is activated in the heating mode if the temperature
Malfunction being sensed by the heat exchanger thermistor exceeds the limit.
Detection
Malfunction Activated when the temperature being sensed by the heat exchanger
Decision rises above 65 .
Conditions
Supposed
Faulty electronic expansion valve
Causes
Dirty heat exchanger
Faulty heat-exchange sensor
Insufficient gas
Troubleshooting * Caution Be sure to turn off power switch before connect or disconnect connector, or
else parts damage may be occurred.
Electrify the machine again and turn it on with the
remote controller, check whether the wind
temperature is below 65
The malfunction is reported
after the machine has run
for some time?
1
Check room temperature and
pipe temperature sensor.
2 the temperature monitoring circuit
of the indoor mainboard
The indoor unit blows poorly
due to blocked filters or poor
condition of the fan?
1) Clean the filters
2) Reinstall the fan.
Use some tools to measure the pressure of system
YES
NO
YES
NO
Service diagnosis
Domestic air conditioner
48
Содержание 2U40S2SM1FA
Страница 11: ...Pinping diagrams Domes t ic air condit ioner 4 Pinping diagrams 9 ...
Страница 12: ...Operation range Domestic air conditioner 5 Operation range 10 10 0 21 27 35 20 40 60 43 20 40 ...
Страница 15: ...wiring diagram Domestic air conditioner PCB 1 13 NOTE J3 OFF STATUS ...
Страница 16: ...wiring diagram 14 Domestic air conditioner PCB 2 ...
Страница 33: ...Dimensional drawing 31 Domestic air conditioner 8 Dimensional drawings 9 Center of gravity ...
Страница 63: ...Domestic air conditioner Sincere Forever ...
Страница 64: ...Wall Mounted Type DC Inverter FREE MATCH N Series 2U40S2SM1FA Model No ...