RC-122 / RC-122B Two Stage Heat/Cool 

2 Stage Heat / 2 Stage Cool

 

 Thermostat Installation Instructions 

 
DESCRIPTION 
 
The RC-122 is a precision digital thermostat designed for 24 VAC two-stage heating and cooling systems.  It 
offers programmability, stand-alone operation, and robust, optically isolated communications with automation 
systems, utility control systems, and personal computers.  The RC-122B is equipped with a “cool blue” 
backlight display. 
 
Electrical rating: 

 

24 V; 3 A; 50/60 Hz 

Maximum current: 

 

2 A on any circuit, 3 A total 

Thermostat operating current:  

less than 15 mA 

 
The following requirements must be observed for installation in Europe:  CE 
 

1.

 

This equipment must be installed in accordance with National wiring rules for the country in which it is 
installed. 

2.

 

Fuses must be replaced only with IEC rated components. 

3.

 

All product labels, instructions and markings relating to safety must be translated to a language, which is 
acceptable in the country in which this equipment is to be installed. 

 
INSTALLATION 
 
Before installing this thermostat: 
 

1.

 

Read all of the installation instructions carefully. 

2.

 

Read the Owner's Manual carefully. 

3.

 

Ensure that this product is suitable for your application. 

4.

 

Ensure that wiring complies with all codes and ordinances. 

5.

 

Disconnect power to the control transformer to prevent electrical shock and damage to equipment. 

6.

 

Select an appropriate location to ensure an accurate temperature reading. 

 

Location 

 
When replacing an existing thermostat, install the RC-122 in the same location.  If the existing location doesn't 
meet the following criteria, choose a new location.  When choosing a location for the thermostat: 

 
1.

 

Ensure that the thermostat is mounted 5 feet above the floor and is at least 2 feet from an outdoor wall. 

2.

 

Ensure that the thermostat is located in an area where there is adequate air circulation. 

3.

 

Do not mount in the path of direct sunlight or of radiant heat generated by appliances. 

4.

 

Do not mount behind an outdoor wall, near a fireplace, or in the path of any air ducts. 

 

 

Document Number 13I00-17 / Rev B / April, 2004 

Copyright 

 1999-2004 Home Automation, Inc. 

All Rights Reserved

 

Содержание OMNISTAT RC-122

Страница 1: ...this equipment is to be installed INSTALLATION Before installing this thermostat 1 Read all of the installation instructions carefully 2 Read the Owner s Manual carefully 3 Ensure that this product i...

Страница 2: ...ING When mounting the RC 122 grasp the thermostat by the sides avoiding the keys and unsnap the base from the face Holding the base to the wall so that the word TOP is upright and facing you 1 Mark th...

Страница 3: ...ation See Figures 7 8 Insert the cable into the connector on the thermostat circuit board marked COMM Upon completion of wiring the thermostat push all excess wiring into the hole in the wall Plug the...

Страница 4: ...Connect power to the transformer and system The display will show all segments for about 5 seconds 4 Press the Fan key The fan should come on Press the Fan key again The fan should go off 5 Press Hol...

Страница 5: ...5 5 Figure 5...

Страница 6: ...2 To configure the display backlight to always be on set the JP2 Select Backlight Mode jumper to the ON position between the middle and bottom pin on the connector See Figure 6 3 To configure the dis...

Страница 7: ...s item 5 Use the arrow keys to change the value of each item 6 Do not set the values to anything other than the specified range for each item 7 To exit Setup mode press the Fan key The thermostat will...

Страница 8: ...fficient Control EEC should be turned on settings 0 1 4 and 5 If the system is equipped with a highly efficient second stage you may want to turn EEC off settings 8 9 12 and 13 The thermostat will act...

Страница 9: ...t setting is 51 06 Heat setpoint limit This item is used to limit the temperature setting in heat mode The desired heat setting can never be set above this setting The default setting is 91 07 Not use...

Страница 10: ...t is running faster or slower than the actual time you can have the thermostat automatically compensate up to 29 seconds per day The thermostat will add or subtract the selected amount of time daily 1...

Страница 11: ...he thermostat QUICK REFERENCE SETUP GUIDE This table displays each Installer Setup item with its default setting The column labeled CURRENT can be used to write down the current settings if any change...

Страница 12: ...roller can send commands to the thermostat to change mode cool setting heat setting status of fan and hold and other items Run a 3 or 4 conductor wire from the HAI system to the thermostat location Al...

Страница 13: ...TCHES The thermostat can be connected to a remote system or remote switch A signal can be sent from the remote location to change the thermostat temperature settings from the DAY setting to the NIGHT...

Страница 14: ...piece of tape Figure 8 Hookup to remote Day Night setback switch OTHER SYSTEMS For connections to personal computers utility management systems and other automation systems refer to connection diagra...

Страница 15: ...at keys for test remove jumper SYMPTOM ACTION TO TAKE 1 Check COMM connector and wiring 2 Check thermostat address setting 3 Check communications mode setting Control By Remote System Not Working 4 Ch...

Страница 16: ...d due to severe weather Stage 2 On Too Often 2 EEC is disabled SYMPTOM ACTION TO TAKE 1 System may be equipped with an outdoor thermostat which is overriding Stage 2 the when outdoor temperature is mi...

Отзывы: