7.2.4.11 Function test for the electrical wiring connections
The energy meter must be connected to the voltage supply and a
load must be connected. This function can only be used if the power
factor of the installation is between 0.6 and 1 and minimum current
consumed on each phase = 20 % In.
Press and hold button B for at least 3 seconds.
The messages below indicate you the connection status of phases
in the meter device.
Press button B for at least 3 seconds to exit this mode.
x1 (3s)
Error
Error description
Err 0
no error
Err 1 / 2 / 3
Reverse polarity of current transformer on phase 1/phase2/phase3
Err 4
Reversed polarity of voltage between V1 and V2
Err 5
Reversed polarity of voltage between V2 and V3
Err 6
Reversed polarity of voltage between V3 and V1
Err 7
reversed connection of voltage between V1 and neutral conductor
Err 8
reversed connection of voltage between V2 and neutral conductor
Err 9
reversed connection of voltage between V3 and neutral conductor