Assembly
Technical changes reserved
39
6.7
Dismantling the fan unit
The work must only be performed by an electrically skilled
person.
Position of the fan unit on the fire safety hous-
ing
Step
Action
1
-
Disconnect all the poles of the fan unit from the electricity supply and verify
compliance with VDE 0100 for the 230 V mains connection before assem-
bly.
-
Verify the absence of voltage.
WARNING! 230 V AC
Dangerous voltage. May
result in death, severe in-
jury or extensive material
damage.
2
Disconnect the temperature sensor and remove.
-
Release the two contacts on the terminal strip using a flat-head screwdriv-
er. Pull the temperature probe and cable out of the housing.
-
Seal the remaining holes with mineral wool.