About the fire safety housing
8
Technical changes reserved
3
About the fire safety housing
Coding
FBxx
L
E
30 minutes' fire resistance
FBxx
S
E
90 minutes' fire resistance
FB
2
xLE/FB
2
xSE
Floor-standing housing
FBxxLE/FBxxSE
Surface-mounted wall mounting
Properties
-
Floor-standing housing (FB2xLE/FB2xSE) or surface-mounted wall mounting
(FBxxLE/FBxxSE)
-
Door can be taken off the hinges to reduce weight during transport
-
Door locking via swivel lever with two-way key bit
-
Cable entry at the top and bottom
-
Cable bulkhead for single entry
-
External fastening lugs
-
Door closes flush with body, opening angle 180°
-
Ventilation in the housing rear panel
-
C-rails for the direct installation of mounting plates or device carriers
Protection type IP44
ATTENTION
Protection type IP44 is only achieved if the fire safety housing is
mounted on a suitable wall.
The wall and floor must meet fire resistance class F30 or F90.
If the fire safety housing is set up as a free-standing unit, an additional
rear panel must be installed. This must be ordered as an additional item.
Scope of delivery
-
The scope of delivery includes everything that is required and logical for
installation.
-
The fire safety housings are delivered as described in the catalogue. Please
refer to the catalogue for ordering options.
-
230 V fan which switches off automatically in the event of a fire.
-
Smoke detector with switch socket connection to fan (fan switches off when
smoke is detected - for use in escape routes).
-
Fan unit with integrated smoke detector.