background image

6L

E

00

28

26

A

z

Programmable light

sensitive switch

s

EE110, 04011

Operating principle

The EE110, 04011 programmable light sensi-
tive switch controls light sytems according to
a program set by the user, depending on
natural illumination;
- during the work authorization period,

depending on wheter the measured light
level is below or above the order, it will be
switched on or off.

- during the work banning period, the

contact remains without tension, whatever
the light level is.

The light sensitive switch includes a built
in time delay which avoid unnecessary
switching due to temporary factors such
as car beams etc...

Description

The programmable light sensitive switch EE110,
04011 has two main functions:
• a light sensitive switch comprising:

Œ

Override selector switch to allow permanent
setting ON or OFF , auto or test mode.



Lighting range selector

Ž

Potentiometer to set light level



Indicator to show output switching.

• a programmer to establish the automatic operating
cycle.

Permanent overrides

the override selector

Œ

allows permanent

overrides which have priority on programming
and the measured light level.

permanent override “ON"

permanent override "OFF"

Setting of the working level

the “test” position of the override selector

Œ

makes easier the setting of the working level,
it removes the ON and OFF delay.
Select the sensitivity range which suits whith
the application (selector



) :

5 to 100 lux (low light level) applica-
tion examples : public lighting, shop
windows, signals....

50 to 2000 lux (high light level) appli-
cation examples : control of shades.

At the appropriate moment of the day, put the
selector

Œ

in “test” position; turn the poten-

tiometer

Ž

up to the switching point (the

indicator



lights); put the selector back to

position “auto”, the normal operating mode of
the device.

auto

test

auto

test

Lux

T

6:00

8:00

17:00

23:00

ON

ON

OFF

OFF

OFF

19

18

20

Programming

OFF

ON

Switching dial

Work

banning

period

Work

authorization

period

Time setting

Œ

Ž





L
N

5

18 19 20

6

9 10

Mounting of the cell

To ensure a good working of the light sensitive
switch, the cell must not be influenced by
artificial light or direct solar radiation and has
to be sheltered from dust and humidity.
In case of disconnection of the link between
the cell and the light sensitive switch, the
output of the device will be switched on.

Make sure the light sensitive switch is unplug-
ged before connecting the cell.

Technical specification

Electrical specification:

- Voltage rating :

230V~+10/-15% 50 Hz

240V~+/-6%

- Consumption :

1,5 VA max.

- Output : 1 voltage free changeover contact

Max. breaking capacity :

- AC1

16A 230V~

Incandescent lamp:

2000W 230V~

- Halogen lamp:

1000W 230V~

- Fluorescent lamp:

- Uncompensated 1:

1000W 230V~

- Compensated in series (10µ): 1000W 230V~

// compensated (15µF):

200W 230V~

- Duo :

1000W 230V~

- Action type:

1B

- Pollution category:

2

- Rated impulse voltage:

4 kV

- Software structure:

class A

- Max. altitude:

2000m

- Upstream protection:

circuit breaker 16A

- Voltage and current declared for the needs

of EMC emissions tests:

230V~ / 0.5A

Functional characteristics:

- 2 sensitivity ranges:

5 to 100 lux,

50 to 2000 lux

- Daily cycle:

- Program setting:

15 minutes increments

- Accuracy:

± 6 min./ annum

- Operating reserve:

at 20°C, 200 h after

beeing connected for 120 h

- ON and OFF delay:

15 to 60 s.

- Working temperature :

-30 °C to +60 °C (cell)

-10 °C to +45 °C (modular device)

- Storage temperature:

- 20 °C to +60 °C

- Protection class (cell):

IP54

- Insulation class (cell):

II

- Independent panel-mounted (DIN rail) control

device

Size:

- Dimension (modular):

5

0

17,5 mm x 5

- Dimension (cell):

32 x 48 x 37 mm

Connection capacity:

- Modular device:

0,5 to 4 mm

2

- Cell:

0,75 to 2,5 mm

2

- Max. lenght between cell and modular

device:

50 m

- Mounting of the cell with 2 screws: Ø 2,5 mm.

A warranty period of 24 months is offered on hager

products, from date of manufacture, relating to any mate-

rial of manufacturing defect. If any product is found to be

defective it must be returned via the installer and supplier

(wholesaler). The warranty is withdrawn if:

- After inspection by hager quality control dept the device

is found to have been installed in a manner which is

contrary to IEE wiring regulations and accepted practice

within the industry at the time of installation.

- The procedure for the return of goods has not been

followed. Explanation of defect must be included when

returning goods.

z

Warranty

NOT APPLICABLE FOR AUSTRALIA

Correct Disposal of This product (Waste Electrical &

Electronic Equipment).

(Applicable in the European Union and other

European countries with separate collection sys-

tems).

This marking shown on the product or its literature indicates

that it hould not be disposed with other household wasted at

the end of its working life. To prevent possible harm to the

environment or human health from uncontrolled waste dispo-

sal, please separate this from other types of wastes and recy-

cle it responsibly to promote the sustainable reuse of material

resources.

Household users should contact either the retailer where they

purchased this product, or their local government office, for

details of where and how they can take this item for environ-

mentally safe recycling.

Business users should contact their supplier and check the

terms and conditions of the purchase contract. This product

should not be mixed with other commercial wastes of disposal.

Usable in all Europe

å

and in Switzerland

Load output connection: If load intensity

is >10A use cables with at least a 2.5mm²

diameter

1

6LE002826A

Отзывы: