Installation, Commissioning &
Operating Manual
EN54 APPROVED 2 - 12 ZONE CONVENTIONAL CONTROL
PANEL
Approved Document UI-XLEN-01 Issue 7.0
810a/04
S o f t w a r e V e r s i o n 4 . 0 & A b o v e
www.acornfiresecurity.com
Страница 1: ...sioning Operating Manual EN54 APPROVED 2 12 ZONE CONVENTIONAL CONTROL PANEL Approved Document UI XLEN 01 Issue 7 0 810a 04 S o f t w a r e V e r s i o n 4 0 A b o v e www acornfiresecurity com www aco...
Страница 2: ...uires periodic checks as specified in BS 5839 Part 1 It is the responsibility of the system user to ensure it is regularly serviced and maintained in good working order system user to ensure it is reg...
Страница 3: ...4 ESD PRECAUTIONS 15 GENERAL 15 MOUNTING THE CABINET 15 MAINS CONNECTIONS 16 CONNECTING THE BATTERIES 17 SETUP PROGRAMMING 18 NETWORK PANELS SETUP 18 TWIN WIRE MODE 20 ZONE INTERFACE FUNCTION 21 LEVEL...
Страница 4: ...programmable and there are options to have delays to the outputs The All inputs and outputs are fully programmable and there are options to have delays to the outputs The programming features of the E...
Страница 5: ...lation Commissioning Operating Manual Approved Document Ref UI XLEN 01 Issue 7 0 3 ABOUT THIS PANEL CABINET 60mm 85mm 310mm 455mm 300mm 450mm Fire Detection System www acornfiresecurity com www acornf...
Страница 6: ...nels comprise of two main circuit boards plus optional ancillary boards PSU 28V 0V C NC NO C NC NO FIRE FAULT FR FLT CC PUL OP OP IP IP SNDR1 SNDR2 ZONE1 ZONE2 ZONE3 ZONE4 BATTERY 1 2 3 4 5 6 7 ON 1 2...
Страница 7: ...ZONE D 1 2 3 4 ON D C B A TWIN OPA OPB AUX SNDR A SNDR B C NO TPCA04 S Std spec 4 zone extension card TPCA05 Comms PCB TPCA04 H High spec 4 zone extension card 4 x conventional or Twin Wire zone circ...
Страница 8: ...y maintained fail safe unfused Max 3A 30vdc Programmable O P Programmable O P Alert pulses sounders Precint class change activates sounders Switched ve inputs Switched ve outputs Max load 40mA To 0 vo...
Страница 9: ...ire zone circuits fused 500mA Relay Coil Relay Coil Programmable O P Programmable O P Programmable relay O P unfused Max 3A 30vdc 28v 28v Switched ve outputs Max load 40mA Conventional monitored sound...
Страница 10: ...ach per circuit Ensure 2 4A is not exceeded Zone 1 4 Fire alarm zone circuits Conventionally wired detection circuit or Twin Wire combined detection sounder circuit 4K7 Ohm 5 0 25W EOL resistor Monito...
Страница 11: ...between outputs 2 4A Power supply output voltage 21 27 29 68vdc Tolerance 0 1 Maximum continuous load for battery standby ImaxA ImaxA 610mA ImaxB not specified Minimum current drawn by panel example 4...
Страница 12: ...of 112m2 per device When mounted on a flat ceiling heat detection devices have an individual coverage of 5 3m radius However these radii must overlap to ensure there are no blind spots Therefore indiv...
Страница 13: ...th that cable The screen or drain wire of circuits should be bonded to earth at recommended for use with that cable The screen or drain wire of circuits should be bonded to earth at one location only...
Страница 14: ...under Circuit Wiring 4K7 OHM END OF LINE RESISTOR 4K7 OHM END OF LINE RESISTOR ZONE 1 SNDR1 R L1 L1 L2 IN OUT R L1 L1 L2 IN OUT R L1 L1 L2 IN OUT APOLLO S65 BASE 45681 201 APOLLO S65 BASE 45681 201 AP...
Страница 15: ...rs and call points Note Each zone circuit configuration is set to Conventional by default Twin Wire mode must be set zonally using DIL switches 1 4 on the Main PCB Or switches A B C D on the zone exte...
Страница 16: ...ions of the Act you are therefore requested to take such steps as are necessary to According to the provisions of the Act you are therefore requested to take such steps as are necessary to ensure that...
Страница 17: ...and must be segregated away from mains voltage Any junction boxes used should be clearly labelled FIRE ALARM Any ancillary devices e g door retaining magnets must be powered from a separate power sour...
Страница 18: ...gland must be used to secure the outer sheath of the cable used The earth must first be connected to the primary earth stud peg marked with a symbol using the ring crimp provided Sufficient earth lead...
Страница 19: ...ute check connections The battery charging voltage is factory calibrated to 27 3vdc 0 2v 20o C This should not normally require adjustment Where battery problems are experienced the following informat...
Страница 20: ...top of the Comms PCB to re connect the display board ribbon cable Each panel to be included in the network is defined by setting a switch on the main PCB In the case of the Excel EN this is switch 7 o...
Страница 21: ...B and back to the Master panel again see drawing below This enables the network to still function if there is a break in the cables If replacing an older system where the existing cabling cannot be c...
Страница 22: ...nals 1 SNDR2 ZONE1 ZONE2 ZONE3 ZONE4 1 2 3 4 5 6 7 ON 1 2 3 4 5 6 7 ON 1 2 3 4 5 6 7 ON To set Twin Wire mode for zones 1 4 on the main circuit board move switches 1 4 on the 7 way DIL switch located...
Страница 23: ...ition the last zone becomes 1 1 Non latching Non latching 2 2 Non aux operating Non aux operating Note If the interface zone is also set to Twin Wire mode and sounders are connected to the zone circui...
Страница 24: ...ctive Programming throughout the panel is carried out in a sequence where the fire LEDs indicate the options to set and the fault LEDs indicate the status of these settings Generally button 1 is used...
Страница 25: ...nitoring type for zone Schottky or Zener diode detector bases Sprinkler pump monitoring function 3121 32 Dependancy Modes False Alarm Management Set panel zones to dependancy mode A B or C 2124 2114 2...
Страница 26: ...displayed pressing and holding the ENTER button will reveal which sounder circuit was at fault This is indicated by the fire LEDs 1 6 as per the table below Repeater faults If a repeater fault is dis...
Страница 27: ...er circuit output or delay will now be enabled The panel will bleep to acknowledge the reset When finished enter the next programming code or disable the controls and return DIL switch 6 to OFF RESOUN...
Страница 28: ...buzzer on network slave panel The keypad can be used to activate the panel controls instead of using the key switch The default code is 1 2 3 4 however this can be changed It is also possible to disab...
Страница 29: ...hold button 1 for 3 seconds to exit programming mode 2 1 2 3 The panel delay time for all outputs is set here To actually apply the delay to the desired outputs see programming code 2 3 2 3 The defau...
Страница 30: ...t option or hold button 1 for 3 seconds to exit programming mode 2 1 2 3 The control panel monitors all internal PCBs for correct function If adding or removing any of the additional extension zone ca...
Страница 31: ...ng default LED 1 ON legacy radial circuit monitoring Press the ENTER button zone 6 fire LED will pulse to indicate edit mode Now use button 2 to change the setting indicated by the amber fault LED ON...
Страница 32: ...d When finished press the ENTER button again and the zone 7 fire LED will return to steady view mode Press button 1 to move to next option or hold button 1 for 3 seconds to exit programming mode 2 1 2...
Страница 33: ...n one go When finished press the ENTER button again and the zone 10 fire LED will return to steady view mode Press button 1 to move to next option or hold button 1 for 3 seconds to exit programming mo...
Страница 34: ...alarm at the panel with no local sounder circuit operation Priority alarm EN54 Normally a 220R call point will override delays or dependency alarms This option allows turning off the priority alarm f...
Страница 35: ...editing mode The fire zone 1 LED will now pulse to indicate the editing of attribute 1 fire latching for the selected zone Use button 1 to scroll to the attribute that requires editing inidicated by a...
Страница 36: ...will not operate Alarm sounder circuits will not operate The indication is non latching Gate valve closed via 470 resistor The panel will operate as per open or short circuit fault except that Genera...
Страница 37: ...r Zone Function Settings programming mode 3 1 2 1 With the required zone for editing LED lit press the ENTER button to enter editing mode The fire zone 1 LED will now pulse to indicate the editing of...
Страница 38: ...te at the control panel but not activate the sounders The first detector alarm will indicate at the control panel but not activate the sounders 2 2 The panel resets and re checks the inhibited zone wi...
Страница 39: ...ode and press ENTER The fire LED 1 will light indicating changing the timing for the confirmation time 1 4 minutes Use button 1 to move to fire LED 2 for changing the timing for the auto reset time 5...
Страница 40: ...fire LED to zone 3 Use button 1 to move the fire LED to zone 3 Press the ENTER button Press the ENTER button to enter edit mode and zone 3 fire LED will pulse to enter edit mode and zone 3 fire LED w...
Страница 41: ...NTER button again will toggle the status indicated by a rapid or slow pulsing LED see below Then use Button 1 to move to the next zone If the zone has been set to not resound alarms the LED will be of...
Страница 42: ...les between all sounder circuits all aux outputs or all sounder circuits and all aux outputs The selection is indicated by the Sounder Status LED and the Aux Output Status LED When finished programmin...
Страница 43: ...ove to zone 2 fire LED for setting the function of the PUL input and then back to zone 1 again The current setting for the input will be indicated by the amber fault LEDs as per table below With the r...
Страница 44: ...fault occurs for fail safe operation To set either of the two miscellaneous options above or to make outputs programmable enter the above code and press ENTER The fire zone 1 LED will now pulse to ind...
Страница 45: ...The setting of the output is indicated by the amber fault LED ON OFF or PULSING RESOUND SILENCE RESET ENTER 1 2 3 4 Disable Mode Test Mode Mute Buzzer Test Lamps RESOUND SILENCE RESET ENTER 1 2 3 4 Di...
Страница 46: ...he setting of the sounder circuit is indicated by the amber fault LED ON OFF or PULSING RESOUND SILENCE RESET ENTER 1 2 3 4 Disable Mode Test Mode Mute Buzzer Test Lamps RESOUND SILENCE RESET ENTER 1...
Страница 47: ...o selected zones in the same way as the other outputs and sounder circuits The process is exactly the same as with the other outputs and sounder circuits but using the above code I e Use button 1 to s...
Страница 48: ...card 1 Zones 5 8 OPB Zone ext card 1 Zones 5 8 Aux Relay Zone ext card 1 Zones 5 8 OPA Zone ext card 2 Zones 9 12 OPB Zone ext card 2 Zones 9 12 Aux Relay Zone ext card 2 Zones 9 12 Use button 2 to c...
Страница 49: ...h the relays switched ve outputs but using the above code I e Use button 1 to select the Twin Wire sounder circuit first indicated by a steady fire zone LED press ENTER and then use button 1 to select...
Страница 50: ...se button 2 to change the response indicated by the amber fault LED Each press of button 2 will toggle through the 3 available responses RESOUND SILENCE RESET ENTER 1 2 3 4 Disable Mode Test Mode Mute...
Страница 51: ...s option enables the default to be changed for each of the local Twin Wire sounder circuits The response can be either CONTINUOUS PULSING or NONE when a fire condition is received from any other panel...
Страница 52: ...ed by the amber fault LED ON or OFF Then use button 1 to move to the next function if required Press the ENTER button to return back to the output selection indicated by a steady zone fire LED When fi...
Страница 53: ...en the panel will automatically exit the diagnosis mode Pressing button 2 will reveal the origin of a system fault indication Note After power up the system should be allowed to initialise for 2 3 min...
Страница 54: ...panel will need to be programmed for the number of repeater panels on the system See panel wide settings 2 1 2 3 option 2 Set Number of Repeater Panels on System Addressing Each repeater panel needs t...
Страница 55: ...on common fire and o p 2 is set to activate for common fault There are 4 programming options available for the inputs and outputs in the repeater panels Outputs 1 6 activate on common fire Outputs 1 6...
Страница 56: ...e the controls is enabled by default but can be disabled in the Level 3 engineering functions To activate the controls using the key switch Turn the key clockwise to the On position The Access Level i...
Страница 57: ...ENTER This button is used to confirm code entries It can also be used for fault diagnosis see FAULT DIAGNOSIS section LED On LED Pulsing Zones in Fire 1 12 N A Indicates alarm condition in zone Zone F...
Страница 58: ...Pressing the button once more will move the selection back to Zone 1 again When the desired circuit outputs or delays to be disabled is indicated by a slow pulsing LED use the ENTER button to select...
Страница 59: ...l move the selection back to Zone 1 again When the desired zone to be tested is indicated by a slow pulsing LED use the ENTER button to select it Once selected the indicator LED will change to a rapid...
Страница 60: ...ter pressing ENTER LED Off after pressing ENTER Location Zone 1 Fire LED off Sounder circuit 1 short circuit Sounder circuit 1 open circuit OK Main PCB SNDR 1 Zone 2 Fire LED off Sounder circuit 2 sho...
Страница 61: ...ts will still function Main Board or zone extender boards System Fault LED continous and General Fault LED pulsing and continous buzzer sound Main board or extender card if fitted are halted Fault rel...
Страница 62: ...part of BS 5839 THE NEED FOR MAINTENANCE ROUTINE MAINTENANCE TESTING DUTIES OF THE RESPONSIBLE PERSON The system user needs to appoint a single named member of the premises management to supervise all...
Страница 63: ...lectrical contractor or fire alarm specialist Inspection servicing visits are normally conducted on a quarterly basis unless such factors as a dirty environment warrant servicing on a more regular bas...
Страница 64: ...R TIME OF TEST SCHEDULE OF TESTING This Section To Be Used To Record ALL Weekly Tests Of The Fire Alarm System Excel EN Installation Commissioning Operating Manual Approved Document Ref UI XLEN 01 Iss...
Страница 65: ...R TIME OF TEST SCHEDULE OF TESTING This Section To Be Used To Record ALL Weekly Tests Of The Fire Alarm System Excel EN Installation Commissioning Operating Manual Approved Document Ref UI XLEN 01 Iss...
Страница 66: ...R TIME OF TEST SCHEDULE OF TESTING This Section To Be Used To Record ALL Weekly Tests Of The Fire Alarm System Excel EN Installation Commissioning Operating Manual Approved Document Ref UI XLEN 01 Iss...
Страница 67: ...R TIME OF TEST SCHEDULE OF TESTING This Section To Be Used To Record ALL Weekly Tests Of The Fire Alarm System Excel EN Installation Commissioning Operating Manual Approved Document Ref UI XLEN 01 Iss...
Страница 68: ...ITS Excel EN Installation Commissioning Operating Manual Approved Document Ref UI XLEN 01 Issue 7 0 66 Fault Reason For Call Out Action Taken Date Work Completed Engineer s Details www acornfiresecuri...
Страница 69: ...ITS Excel EN Installation Commissioning Operating Manual Approved Document Ref UI XLEN 01 Issue 7 0 67 Fault Reason For Call Out Action Taken Date Work Completed Engineer s Details www acornfiresecuri...
Страница 70: ...ITS Excel EN Installation Commissioning Operating Manual Approved Document Ref UI XLEN 01 Issue 7 0 68 Fault Reason For Call Out Action Taken Date Work Completed Engineer s Details www acornfiresecuri...
Страница 71: ...t has caused the alarm A detector will have a In the event of a false alarm look for the device that has caused the alarm A detector will have a red LED lit or check to see if a call point glass is br...
Страница 72: ...www acornfiresecurity com www acornfiresecurity com...