Operation—Foundation Fieldbus
50
6.2.2.3 Data processing
Use the L_TYPE parameter to apply a linearization function to the data.
• Direct—data is sent directly from the TB to the AI without
processing. The units for the XD_SCALE and OUT_SCALE
parameters must be identical.
• Indirect—data from the TB is linearly scaled from the input scale
(XD_SCALE) to the output scale (OUT_SCALE).
• Indirect square root—data is rescaled from the input scale
(XD_SCALE) and recalculated using a root function. Then the
value is linearly scaled to the output scale (OUT_SCALE).
6.2.2.4 Alarms
The AI block can generate block alarms and limit alarms. Use the
ACK_OPTION parameter to specify if an alarm must be acknowledged.
When the measured value status is “bad”, the AI block BLOCK_ERR
parameter indicates an Input Failure.
•
Block alarms
—a block error will be reported via the
BLOCK_ERR parameter (simulate active, input failure, block
configuration error, out of service (OOS)). The BLOCK_ALM
parameter sends the alarm status to the control system.
•
Limit alarms
—the measured value OUT falls outside of the limit
values (HI_HI_LIM, HI_LIM, LO_LIM, LO_LO_LIM).
If an alarm occurs, evaluate the following bus parameters:
• OUT parameter (currently measured value) in the Al block
• LAST_ERROR parameter in the transducer block
• SENSOFACE_STATUS parameter in the transducer block
Содержание si792 D series
Страница 2: ...2 ...
Страница 6: ...Table of Contents 4 ...
Страница 12: ...Specifications 10 ...
Страница 36: ...Interface and navigation 34 ...
Страница 44: ...Operation si792 x D 4 20 mA HART 42 ...
Страница 66: ...Operation Foundation Fieldbus 64 ...
Страница 72: ...Operation Profibus PA 70 ...
Страница 80: ...Maintenance 78 ...
Страница 86: ...Troubleshooting 84 ...
Страница 88: ...Parts and accessories 86 ...
Страница 93: ...Index 91 Z zero adjustment 72 ...
Страница 94: ...Index 92 ...
Страница 95: ...93 ...