6
Figure 1 Installation suggestions for a 1200 mm deep rack (top view)
(1) 1200 mm (47.24 in) rack depth
(2) A minimum of 50 mm (1.97 in) between the front rack posts and the front rack door
(3) 780 mm (30.71 in) between the front rack posts and the rear of the chassis, including power supply
handles at the server rear (not shown in the figure)
(4) 800 mm (31.50 in) server depth, including chassis ears
(5) 960 mm (37.80 in) between the front rack posts and the CMA
(6) 860 mm (33.86 in) between the front rack posts and the rear ends of the slide rails
Installation site requirements
Space and airflow requirements
For convenient maintenance and heat dissipation, make sure the following requirements are met:
•
A minimum clearance of 635 mm (25 in) is reserved in front of the rack.
•
A minimum clearance of 762 mm (30 in) is reserved behind the rack.
•
A minimum clearance of 1219 mm (47.99 in) is reserved between racks.
•
A minimum clearance of 2 mm (0.08 in) is reserved between the server and its adjacent units in
the same rack.