Appendix D Environment requirements
About environment requirements
The operating temperature requirements for the server vary depending on the server model and
hardware configuration. When the general and component-based requirements conflict, use the
component-based requirement.
Be aware that the actual maximum operating temperature of the server might be lower than what is
stated because of poor site cooling performance. In a real data center, the server cooling
performance might decrease because of adverse external factors, including poor cabinet cooling
performance, high power density inside the cabinet, or insufficient spacing between devices.
General environment requirements
Item
Specifications
Operating temperature
Minimum: 5°C (41°F)
Maximum: 45°C (113°F)
CAUTION:
The maximum temperature varies by hardware option presence. For more
information, see "
Operating temperature requirements
Storage temperature
–40°C to +70°C (–40°F to +158°F)
Operating humidity
8% to 90%, noncondensing
Storage humidity
5% to 95%, noncondensing
Operating altitude
–60 m to +5000 m (–196.85 ft to +16404.20 ft)
The allowed maximum temperature decreases by 0.33 °C (32.59 °F) as the
altitude increases by 100 m (328.08 ft) from 900 m (2952.76 ft). HDD drives
are not supported at an altitude over 3000 m (9842.52 ft).
Storage altitude
–60 m to +5000 m (–196.85 ft to +16404.20 ft)
Operating temperature requirements
Table 11 Operating temperature requirements
Maximum server operating
temperature
Hardware options
30°C (86°F)
One fan fails when processor 6146 or 6246, or a processor with a
TDP of more than 200 W is installed.
35°C (95°F)
One fan fails when processor 6144 is installed.
40°C (104°F)
Processors with a TDP not more than 165 W are supported,
excluding processor 6146 and 6246.