power is supplied to the emergency driver.
2.
This product is for use with an LED lighting load and supplies up t
o 7W / 12
W /
25
W
constant
power
with
output
voltage between 0 VDC and
0 VDC in emergency mode for a minimum of 90 minutes.
5
20
3.Make sure all connections are in accordance with the National Electrical Code or Canadian Electrical Code
and any local regulations.
converter connector of the emergency driver before servicing.
5.This emergency driver is for factory installation and
.
field Installation
6.This product is suitable for use in damp locations where the ambient temperature is 5ºC minimum, +50ºC
maximum. Product is not suitable for heated air outlets and wet or hazardous locations.
9
.
Use with grounded, UL Listed, damp location rated fixtures and
10.The Driver is intended for ordinary locations and for permanent
Contact the manufacturer for information on service.
12.The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition
16.Equipment
should be m
ounted
in locations and at heigh
ts
where it
will
not
be
subjected
t
o tampering
by unauth
orized
personnel.
Contains
LiFePO4
Rechargeable Battery.
Must be recycled or
disposed of properly.
Page
1
of
4
STEP 1
INSTALLING THE EMERGENCY DRIVER
> Disconnect AC power from the LED luminaire.
>
Mount the emergency LED driver by the mounting tabs using the supplied screws
. Th
e luminaire’s
installaion instructions may provide guidance on the recommended mounting location.
>
This product has been designed to reliably interface with a wide selection of LED loads.
. However,
compatibility
cannot be guaranteed with all current
Installation of this emergency LED driver will vary based on the luminaire type, however, generally
follow these steps:
NOTE: After installation, it will be necessary to measure the egress lighting illumination levels to ensure it
complies
with
national, state, and local code requirements.
Page
2
of
4
Make sure the necessary branch circuit wiring is available. An unswitched
source of power is required. The emergency driver must be fed from the same
If used in conjunction with an AC driver
, this distan
ce is up to half the distance the AC driver manufacturer
recommends remote mounting the AC driver from the LED Load
. If
used without an AC driver
, con
sult
installation into one or more Listed
11.
1.To prevent high voltage from being present on yellow & orange output leads prior to installation,
converter connector must be open. Do not join converter connector until installation is complete and AC
13.Do not use this product for other than intended use.
8.Do not install near gas or electric heaters,Do not use outdoors.
14.Servicing should be performed by qualified service personnel.
15.Only apply to LED Driver with the output current less than 3A.
branch circuit as
NOTE:
factory fo
r
r
e
m
o
te
m
o
un
t
in
g
distances
.
and
future
LED
systems
.
Compatibility
testing
of. the end-use system is suggested. Please contact the factory with any questions.
1. Ensure the LED load’s rated power is greater than or equal to the power output of this emergency LED
driver. This is to ensure that this emergency product will not produce more power than the LED load can
handle, thus ensuring that the LED load will not be damaged when the system is in the emergency mode.
is
eligible
for
field
installation.
2. Verify that the forward voltage of the luminaire’s LED array is within the limits of this emergency LED
voltage of the LED array is commonly designated as Vf and should be found on the
forward voltage is within the limits of this product. Using
voltage across the LED arrays when operating
driver. The forward
luminaire markings, in the luminaire
a voltage meter, it may be possible to directly measure the
from the AC driver.
3. Ensure the output current of the LED driver does not exceed
3
Amps.This is the current into
doing the following:
be
biven
in
lumens per watt (lm/w).
load. In many cases the actual lumen output in emergency mode will be greater than this
b.
calculation gives, however it will provide a good estimate for beginning the lighting design of the system.
C. Using the results of this calculation and industry standard lighting design tools, calculate the
a
nticipated illumination levels in the path of egress.
Lumens In Emergency Mode = Lumens per Watt of Fixture * Output Power
Emergency
LED
driver
________________
(Lumens) =
(lm/W) *
(W)
________________
case should be grounding.
3A max.
6W max.
50~200VDC
0.5A(@50Vdc) ~
0.125A(@200Vdc)
25W
LiFePO
4
battery
19.2V 3200mAH
90 Minutes
36 Feet
(11.0m)
120-277VAC
50/60Hz
OUTPUT
Input Voltage
Input Power
Output Voltage
Range
Output
Current
Output
Power
Battery
Emergency
Operation
Max. mounting
height
I
NPUT
LED Driver
output current
120-277VAC
50/60Hz
3A max.
4W max.
50~200VDC
0.14A(@50Vdc) ~
0.035A(@200Vdc)
7W
LiFePO
4
battery
6.4V 3200mAH
90 Minutes
21 Feet
(6.4m)
3A max.
5W max.
50~200VDC
0.24A(@50Vdc) ~
0.06A(@200Vdc)
12W
LiFePO
4
battery
9.6V 3200mAH
90 Minutes
23 Feet
(7.0m)
120-277VAC
50/60Hz
(See electrical data table)
the blue wire.
emergency luminaires.
LED Emergency Conversion Power Pack
For Field or Factory Installation
LCPSD-HV / EMPHV-SD SERIES
NOTICE:
The LCP/EMP/LEDRV Series LED Emergency Driver Power Packs are rated for operation with an internal
pack ambient between 5°C to 50°C. To meet this rating, warranty condition and ensure optimum
component life, it is recommended that the pack be mounted remotely from the light fixture or high
ambient temperatures. Where it is necessary to mount directly to the light fixture, the installer
should verify that the stabilized light fixture surface temperature rise does not contribute radiant
heat directly to the pack surface; resulting in the pack internal ambient temperature exceeding the
max. 50°C rating. Locate or space the pack as necessary.
H3 Group Inc. 1-800-967 5541
Verify LED Luminaire Compatibility
Installation
LCPSD7HV
EMP7HV-SD
LCPSD12HV
EMP12HV-SD
LCPSD25HV
EMP25HV-SD
Do not attempt to service the battery. It is sealed unit and the battery is not replaceable.
The emergency driver with cable conduit is suitable for remote mounting from the luminaire;
the emergency driver without cable conduit is not suitable for remote mounting.