8. Readings on LCD display
°C, °F
reading next to this symbol is measured temperature or error state of value
%RH
reading next to this symbol is measured relative humidity or error state of value
CO2 ppm
reading next to this symbol is measured concentration of CO
2
or error state of value.
°C / °F DP
reading next to this symbol is calculated dew point temperature or error state of value
g/m
3
reading next to this symbol is calculated absolute humidity or error state of value
g/kg
reading next to this symbol is calculated specific humidity or mixing ratio (depends on device
setting) or error state of value
3
this symbol is on if jumper is closed
If specific enthalpy is selected, there is shown only value (number) without corresponding unit.
9. Preventive maintenance and calibration
Pay heed to recommended calibration interval. Do not subject the device to mechanical stress.
10. Technical specification
10.1. Technical parameters
10.1.1. Common parameters
Power voltage:
9 to 30 V DC
Power consumption:
1W during normal operation
4W for 50ms with 15 s period
Measuring interval:
temperature, relative humidity . . . . . 0,5s
concentration of CO
2
. . . . . . . . . . . . 15s
Display switching interval
: 4 s (when more than two values are displayed)
RS485 interface:
receiver – input resistance 96kΩ
max. 256 devices on bus
Relay outputs:
Amount: 2
Maximal voltage: 50 V
Maximal current: 2A
Maximal power: 60 VA
Relays contact is not designed for direct control of line voltage!
(relay contact parameters: max 220Vdc, 125Vac, 2A, 60 W, 62.5 VA)
EMC:
EN 61326-1, EN 55011