background image

Specifications are subject to change without notice.

AR006664 and 

AR004418

 interior transmitters 

with analog outputs

PRODUCT DESCRIPTION 

Programmable interior transmitters

 with 4 - 20 mA or 0 - 10 V outputs are designed for measurement of CO

2

 concentration in air and 

for measurement of air temperature in exacting interiors in building energy management and HVAC systems.  

The CO

2

 concentration 

is measured using the dual wavelength NDIR sensor with multiple point adjustment.

 

This principle compensates 

aging of the sensing elements and guarantees outstanding high reliability and long-term stability of the measurement. 

Measured values

 are displayed on a two-line LCD display. The device is also equipped with three-color LED for visual indication of the 

CO

2

 concentration. Using 

TSensor

 software (see 

www.guilcor.com

you can set up measuring range of device output, measurement

mode  of  CO

2

  concentration  and  limits  of  CO

2

  LED  indication.  For  device  connection  to  USB  port  of  PC  is  used 

AR006576

  cable

(optional accessories). The connector for 

AR006576 

cable connection is situated on the front part of the device near the info-button.

Transmitters are designed

 for easy installation on ordinary KU68 wiring boxes with using two enclosed mounting screws. 

type * 

output  

measured values    

construction 

mounting 

AR006664

2 x 4-20mA 

T + CO

2

 

ambient air 

wall 

AR004418

2 x 0-10V   

T + CO

ambient air 

wall 

f

*  models marked Txxxx

Z

 are custom - specified devices

   T…temperature,  CO

2

…concentration of CO

2

 in air 

INSTALATION AND OPERATION 

For correct function there is necessary to find proper device place. It shouldn’t be placed at places where it can be affected by sunshine, 
near radiators, heating elements and other heat sources, air handlers, windows, doors, into racks and shelves and similar places. For 
buildings with less thermal insulation there is not suitable to place them on external walls of building. If there are communication conductors 
placed into conduit, there is strongly recommended make it caulk, to restrict air flow around device. 
Current  outputs  4  -  20 mA (transmitter 

AR006664

) can  be galvanically  isolated  or galvanically  non-isolated.  Configuration  jumpers

(see schematic diagram) are located on the front part of the device. Voltage outputs 0 - 10 V (transmitter 

AR004418

) are not

galvanically isolated. 
Firstly mount back part of device onto wiring box with two holding screws. Connect cables to terminals and finally insert front part of 
device  (installation  procedure  see  next  page).  For  transmitter  connection  it  is  recommended  to  use  shielded  cable.  Maximum  cable 
length of the current  loop  is  1200m,  maximum  voltage  output  cable  length  is  15m.  All  cables  should  be  located  as  far  as  possible 
from  potential interference sources. 
After powering on the device starts the internal test. During this time LCD display shows  

---- 

 instead of CO

2

 concentration value

.

 

Devices don´t require special operation and maintenance. We recommend you periodic calibration for measurement accuracy validation.

INFO MODE 

The output range settings can be verified without a use of the computer by pressing button on the left side 

of the device (see picture). For button pressing use thin instrument (paper clip etc.). First short press shows 
low range and type of measured value for  I1 output. Next button press  shows values for upper scale limit 

(the  same  channel,  the  same  value).  I2  output  settings  are  displayed  similarly.  No  measurement  and 
communication is possible during info mode. If device stays in info mode for longer than 15 s, device 
automatically returns to measuring cycle. 

ERROR STATES 

Device continuously checks its state during operation and if an error appears, it is displayed relevant code: 

Err 2 

- CO

2

 concentration or temperature measurement error occurred 

Err 0, Err 1, Err 3 

and 

Err 4

 - it is a serious error, please contact distributor of the device 

SAFETY INSTRUCTIONS 

- Don’t connect or disconnect transmitter while power supply voltage is on.
- Don´t use the device in an explosive environment.

- Devices are not designed for locations with chemically aggressive environment.
- Installation, electrical connection and commissioning should be performed by qualified personnel only.

- Devices contain electronic components, it needs to liquidate them according to currently valid conditions.
-