Chapter 6 Specification of Parameters
GK600 User Manual
- 226 -
H0-05
Master/Slave option
Range: 0~2
Factory default: 0
0: PC controls this drive
PC as master controls this drive. This supports all communication protocols.
1: As master
According to the selection of H0-06, the drive sends current b0-02 (digital setting of master
frequency) or F0-01 (PID digital setting) through communication. As master, this drive can
only send the data and cannot receive the data.
2: As slave
Put the received data into b0-02 (digital setting of master frequency) or F0-01 (PID digital
setting) through communication. b0-02/F0-01 is selected by parameter H0-06. Other
communication data addresses are not supported. As slave, this drive can only receive the
data.
H0-06
Frequency setting address
when master controlling slave
Range: 0~1
Factory default: 0
0: b0-02
1: F0-01
This parameter takes effect when H0-05 is set to 1. This parameter sets the slave drive
frequency setting address when this drive is working as the master drive.
H0-07
Proportional factor of received
frequency
Range: 0.0~1000.0%
Factory default:
100.0%
This parameter takes effect when H0-05 is set to 2. Data sent by master is multiplied by H0-07
and then put the result into b0-02 or F0-01 (set by H0-06 of master).
This parameter setting is very useful when a master drive controls a number of slave drives and
needs to allocate the frequency.
Group H1 Profibus-DP communication parameters
Refer to
EPC-CM2 Instruction Manual
for details
Group L Keys and Display of Control Panel
Group L0 Keys of Control Panel
L0-00
MF key setting
Range: 0~6
Factory default: 0
0: No function
1: Forward jog
2: Reverse jog
3: Forward/reverse switchover