Chapter 6 Specification of Parameters
GK600 User Manual
- 224 -
ATTENTION:
When actual length is detected to attain the set length, digital output terminal "length
attained" outputs ON signal no matter the drive is set to stop or not stop. Actual length is
saved at power loss and can be read in both stop and running.
F3-12
Set count value
Range: 1~65535
Factory default:
1000
F3-13
Designated count value
Range: 1~65535
Factory default:
1000
The two parameters are used with digital input terminal "count input" and digital output
terminals "set count value attained" and "designated count value attained". Input pulse through
digital input terminal "count input". When the number of pulses attain the value set by F3-12,
the terminal outputs ON. With the completion of the value of F3-12, the terminal "designated
count value attained” outputs OFF.
When the number of input pulses attains the designated count value of F3-13, terminal
"designated count value attained" will output ON. Upon the completion of set count value of
F3-12, terminal "designated count value attained" outputs OFF.
For example: F3-12= 10, F3-13= 7. Fig. 6-56:
Fig. 6-56
ATTENTION:
Actual count value can be cleared through digital input terminal "count clear". Actual count
value is saved at power loss.
Group H Communication Parameters
Group H0 MODBUS Communication Parameters
Support universal Modbus protocol. Please refer to appendix for detailed description of
communication protocol.