GK600 User Manual
Chapter 6 Specification of Parameters
-
165 -
C1-15
Zero current detection
value
Range: 0.0%~50.0%
Factory default:
5.0%
C1-16 Zero current detection time
Range: 0.01s~50.00s
Factory default:
0.50s
The two parameters should be set with digital output terminal "zero current detection". When
the drive output current is less than the value set by C1-15 and its lasting time attains the value
of C1-16, terminal "zero current detection" outputs ON signal. See Fig. 6-24:
Fig. 6-24
Group C2 Analog and Pulse Input
C2-00
Analog input curve
Range: 000~222
Factory default: 000
Curves of analog input AI1, AI2 and EAI are selected by this parameter.
Ones place: AI1 input curve
0: Curve 1 (2 points)
Defined by C2-01~C2-04.
1: Curve 2 (4 points)
Defined by C2-05~C2-12.
2: Curve 3 (4 points)
Defined by C2-13~C2-20.
3: Curve 2 and curve 3 switchover
Curve 2 and curve 3 selection can be switched via terminal “analog input curve switchover”.
When this terminal is deactivated, curve 2 takes effect, while when this terminal is activated,
curve 3 will work.
时间
输出电流
时间
零电流检测端子
零电流检出水平
零电流检出
时间
运行
停机
Output current
Run
Stop
Zero current detection value
Time
Zero current detection terminal
Zero
current
detection
time
Time