Chapter 6 Specification of Parameters GK600 User Manual
- 158 -
(the highest bit of binary system) through bit0 (the lowest bit of binary system) are as follows:
Table 6-13
Hundreds place
Tens place
Ones place
bit10
bit9
bit8
bit7
bit6
bit5
bit4
bit3
bit2
bit1
bit0
EIA
AI2
AI1
Revd
EX
X6
X5
X4
X3
X2
X1
Ones place: bit0~bit3 : X1~X4
0: Actual terminal takes effect
1: Virtual terminal takes effect
Tens: bit4~bit6 : X5, X6, EX (same as ones place)
Hundreds place: bit8~bit10 : AI1, AI2, EAI (same as ones place)
Virtual terminals simulate actual terminals via communication. Each bit represents one terminal.
When selecting virtual terminal, corresponding bit should be set to 1 in C0-20. Under this
circumstance the actual terminal is invalid.
C0-21
Enabled condition of run
command terminal after
fault reset (RESET)
Range: 0
~
1
Factory default:0
This parameter only takes effect on run command terminals, i.e. digital input terminal set as
1~4 (JOG forward/reverse, run forward/reverse. See table 6-6), and only works for the run after
fault reset.
0: Trigger edge de ON detected
After the fault reset, the drive will start to run when an electric level jump from OFF to ON is
detected and ON signal are maintained.
1: ON detected
The drive will run automatically if ON signal from run command terminal is detected. When
this parameter value is set to 1, please make sure the status of run command terminals
before fault reset operation. Failure to comply may result in equipment damage and/or
personal injury.
Group C1 Digital Output
C1-00
Y1 output function
Range: 0~99
Factory default: 0
C1-01
Y2/DO output function
(when used as Y2)
Range: 0~99
Factory default: 0
C1-02
Control board relay
output function
Range: 0~99
Factory default:
14
C1-03
Option board relay
output function
Range: 0~99
Factory default:
15