Features 

—

 

Providing Max. 16 channels of independent input. 
1-16 selectable. Input signals are insulated from 
the loop. 

—

 

Providing two channels of independent dry contact 
output. 

—

  3-18 consecutive addresses, changing with 

selected channel quantity. 

—

 Power 

supply 

monitored. 

—

 

Cable monitored for open circuit and short circuit. 

Description 

With microprocessor, DI-9309 Addressable 
Multi-Channel Interface can communicate with fire 
alarm control panel (FACP), monitor power supply, 
judge the logic state of input signal, control output and 
state indicators. 

Each output channel occupies an individual address 
and receives start command from FACP, energizes the 
related relay, gives dry contact output and lights the 
related action indicator. Each input is corresponded to 
an address to receive the state signal from the 
equipment and transmit it to FACP. The quantity of 
channels can be set by jumpers. 

Cabling 

Z1, Z2: To the loop of FACP, polarity-insensitive.   
D1, D2: 24VDC power, polarity-insensitive. 
I(n)G: Channel n volt-free normally open input. 
NC1(NC2), COM1(COM2), NO1(NO2): Dry contact 
outputs of Channel I (Channel II). 

Recommended Wiring 

1.5mm

or above fire cable for Z1, Z2, D1, and D2. 

1.0mm

2

 or above fire cable for others. Subject to local 

codes. 

Installation 

Fig. 1 shows dimensions and hole distances.

 

XS3

1

2

3

4

1

00m

m

200mm

90

m

m

190mm

 

Fig. 1 

 

 

Application 

The DI-9309 interface is designed to connect with 
active equipment in field such as water flow switch, 
pressure switch, position switch, signal valve and 
equipment able to transmit back normally open signals. 
It can also connect with the equipment controlled by 
FACP such as fire door, pump, smoke exhaust fan, 
smoke vent, air vent, fire damper and etc.   

1. Setting 

DI-9309 interface can be addressed in field with power 
off by using P-9910B programmer connected to Z1 and 
Z2. Please refer to P-9910B Hand Held Programmer 
Installation and Operation Manual for details. 
Input Channel Setting: Set Channel 1-16 consecutive 
(always beginning from Channel 1) input through 
jumpers inserting to XS3, as shown in Table 1. 

Table 1 

INPUT CHANNEL SETTING 

Pin 

 

Channel QTY. 

4 3 2 1 

1 OFF 

OFF 

OFF 

OFF

2 OFF 

OFF 

OFF 

ON 

3 OFF 

OFF 

ON 

OFF

4 OFF 

OFF 

ON 

ON 

5 OFF 

ON 

OFF 

OFF

6 OFF 

ON 

OFF 

ON 

7 OFF 

ON 

ON 

OFF

8 OFF 

ON 

ON 

ON 

9 ON 

OFF 

OFF 

OFF

10 ON 

OFF 

OFF 

ON 

11 ON 

OFF 

ON 

OFF

12 ON 

OFF 

ON 

ON 

13 ON 

ON 

OFF 

OFF

14 ON 

ON 

OFF 

ON 

15 ON 

ON 

ON 

OFF

16 ON 

ON 

ON 

ON 

Code Range: Occupying 3-18 addresses, the output 
address of Channel 1 can be set within 1

225. The 

output address of Channel 2 is automatically increased 
1 to Channel 1. The input address of Channel n is 
automatically increased n and 1 to Channel 1. For 
instance, the output address of Channel 1 is 15, and 
other addresses are shown in Table 2. 

Table 2 

Input and Output   

Address 

Channel 1 Output 

15 

Channel 2 Output 

16 

Channel 1 Input 

17 

Channel 2 Input 

18 

… … 
Channel n Input 

15+n+1 

The Intelligent Solution 

DI-9309 

Addressable Multi-Channel Interface

 