background image

© 2017 United Technologies Corporation 

1 / 3 

P/N 30310841-EN • REV 001 • ISS 27MAR17 

 

DC-M9416 Series Ceiling 
Mount Sounder Strobe 
Installation Sheet 

 

Description 

The DC-M9416 Series Ceiling Mount Sounder Strobe is a fire alarm 
notification appliance that is designed for mounting on indoor ceilings 
and walls. See Table 1 for a list of model numbers. 

Table 1: Models 

Description 

Model number 

Sounder strobe,15 to 95 multi-
cd, white, with FIRE marking 

DC-M9416W 

Sounder strobe,15 to 95 multi-
cd, red, with FIRE marking 

DC-M9416W 

 

Field-configurable jumper options are available for selecting the 
desired dB output, temporal or steady sound output, and strobe signal 
output. 

The sounder strobe includes a field-configurable switch for selecting 
the desired candela output. The candela output setting is locked in 
place and remains visible after final installation. 

This strobe features an enhanced synchronization circuit to comply 
with the latest requirements of UL 1971 

Signaling Devices for the 

Hearing Impaired

.  

Synchronized operation requires that you connect the DC-M9416 
Series Ceiling Mount Sounder Strobe to a NAC output set for Synch 
Mode, or to a separate DC-M9410 Signal Synchronization Module. 

Installation 

Install and wire this device in accordance with applicable national and 
local codes, ordinances, and regulations. 

WARNING: 

Electrocution hazard. To avoid personal injury or death 

from electrocution, remove all sources of power and allow 10 minutes 
for stored energy to discharge before installing or removing equipment. 

 

Caution:

 Electrical supervision requires the wire run to be broken at 

each terminal. Do not loop the signaling circuit field wires around the 
terminals. 

To install the sounder strobe: 

1.  Remove the cover by depressing the tab on the side of the unit 

with a small screwdriver. Turn the cover counterclockwise to 
release. 

2.  Set the sounder signal, sound output level, and strobe signal to the 

desired settings. See Figure 1. 

3.  Connect the strobe terminals to the signal circuit field wiring. You 

must observe polarity for the unit to function properly. See 
Figure 3. 

4.  Slide the candela switch to the desired candela output (95, 115, 

150, or 177 cd) by aligning it with the indicator below the switch. 
See Figure 2. 

5.  Mount the unit onto a compatible electrical box. See Figure 4. 

6.  Replace the cover by positioning the alignment arrows together 

and rotating the cover clockwise. 

7.  Test the unit for proper operation. 

Figure 1: Sounder and strobe settings 

 

 
(1)  JP1: Sounder signal jumper: Cut to change from temporal to 

steady 

(2)  JP2: Strobe signal output: Cut to change from 1 flash per second 

(public mode) to temporal (private mode) 

(3)  JP3: Sounder sound output: Cut to change from high dB to low dB 

Note: 

If the strobe is set to temporal (private mode), this device is no 

longer UL 1971 but is still UL 1638 Listed. 

Figure 2: Candela switch 

 

(1)  Candela switch 

(2)  Indicator 

 

JP3

JP1
JP2

(1)

(2)

(3)

Отзывы: