background image

HTTP://WWW.HOMBI.RU

 

30307503

                               

                                                                                                    Issue 1.01

 

                                       

 

Features 

—

 

Alarming by pressing, reset by a special key 

—

 Plug-in 

structure 

—

 

Designed to comply with EN 54-11 

Description 

DC-9204 Innovation Manual Call Point (MCP) is 
non-addressable. It alarms by the current caused by 
pressing the action plate. It can be simply connected 
to compatible conventional fire alarm system from 
various manufacturers. This MCP is suitable for public 
places. When there is fire, pressing the action plate on 
this MCP can send alarm signal to compatible 
conventional fire alarm control panel.

 

Connection and Cabling 

Terminals on the MCP base are shown as Fig. 1.

 

I+ I- O+O-

60mm

 

Fig. 1 

I+, I-: Input signal, connecting with compatible control 
panel or the previous MCP. 
O+, O-: Output signal, connecting with the next MCP. 

Recommended Wiring 

0.5mm

2

 or above fire cable, subject to local codes.

 

Installation 

The conduit can be surface mounted or flush 
mounted. 
Surface mounting: 
First install the back box onto the wall using 4 screws, 
then install the base onto the back box. Connect 
cables to corresponding terminals as described above. 
Hook the juts of the MCP body to the base, and then 
press the part below the action plate to combine them 
completely. Fig. 2 shows surface mounting. 

Flush mounting:   

Install the base onto the back box. Then combine the 
enclosure and base the same as surface mounting.  
Fig. 3 shows flush mounting.

 

 

 

Base

MCP

 

Body

Back

 

Box

 

Fig. 2

 

Base

Back

 

Box

MCP Body

 

Fig. 3 

 

Application 

—

 

Application of the MCP is shown in Fig. 4.

 

Output-

Compatible Fire Alarm 
Control Panel

Alarm Zone

O-

O+

I-

I+

To the next device

MCP

Fig. 4 

—

 

Usage of the key

 

Vertically insert the key into the key-hole, then push it 
with force and turn it clockwise. Turn the key back and 
pull it out when the action plate is rebounded. 

 

The Intelligent Solution 

DC-9204 

Innovation Manual Call Point 

0832-CPD-0789

 

548g/03

報 

HTTP://GSTRU.RU

E-MAIL: [email protected]

Отзывы: