Grounding the System
A correctly grounded system protects your equipment from electrical surges and spikes.
CAUTION
Each module must have its own ground connection from a common junction box. Do
not run the earth ground cable between the modules.
NOTICE
The ground resistance levels must comply with local and national electrical codes.
IMPORTANT:
If outdoor connections are used, mount the enclosure as close as possible to the entry point
of the outdoor wiring.
IMPORTANT:
An improper ground connection voids the system’s warranty.
Insert the rod into the ground until a few inches of the tip is left above ground level. Attach the cable to the
rod tip with an appropriate connector. Attach the other end of the cable to a breaker box or a junction box
near the main enclosure.
Figure 2-3
Grounding installation depending on bedrock depth
00000
00000
00000
00000
00000
00000
00000
00000
0000000
0000000
0000000000
0000000000
0000000000
0000000000
000000000
000000000
3
m
(10 FEET)
0.6 m
(2 FEET)
0.6 m
(2 FEET)
> 1.2 m
(47 IN.)
<
1.2 m
(47 IN.)
3
m
(
1
0
F
E
E
T
)
3 m (10 FEET)
MET
ALLIC ROD
BEDROCK
• If the bedrock is more than 3 meters (10 feet) below ground level, drive the grounding rod vertically
3 meters (10 feet) into the ground.
• If the bedrock is more than 1.2 meters (47 inches) below ground level, drive the rod into the ground to
bedrock level and bury the remainder horizontally at least 0.6 meters (2 feet) below ground level.
• If the bedrock is less than 1.2 meters (47 inches) deep, bury the rod horizontally at least 0.6 meters
(2 feet) below ground level.
NOTE:
Refer to your local regulations and practices if an adequate grounding installation isn’t possible.
Rod Specifications for Grounding
The rod specifications are guidelines only. Refer to your national and local regulations for compliance
criteria.
18
895-00677
Agri Alert 128 Touch
Содержание 890-00584
Страница 14: ...NOTES 14 895 00677 Agri Alert 128 Touch...
Страница 20: ...NOTES 20 895 00677 Agri Alert 128 Touch...
Страница 30: ...NOTES 30 895 00677 Agri Alert 128 Touch...
Страница 38: ...NOTES 38 895 00677 Agri Alert 128 Touch...
Страница 44: ...NOTES 44 895 00677 Agri Alert 128 Touch...
Страница 64: ...Chapter 9 Configuring a 0 5 Volt Zone Type 64 895 00677 Agri Alert 128 Touch...
Страница 66: ...NOTES 66 895 00677 Agri Alert 128 Touch...
Страница 82: ...NOTES 82 895 00677 Agri Alert 128 Touch...
Страница 88: ...NOTES 88 895 00677 Agri Alert 128 Touch...
Страница 92: ...NOTES 92 895 00677 Agri Alert 128 Touch...
Страница 96: ...NOTES 96 895 00677 Agri Alert 128 Touch...
Страница 100: ...NOTES 100 895 00677 Agri Alert 128 Touch...
Страница 102: ...NOTES 102 895 00677 Agri Alert 128 Touch...
Страница 106: ...NOTES 106 895 00677 Agri Alert 128 Touch...
Страница 107: ...F Wiring Diagram with Terminals 895 00677 Agri Alert 128 Touch 107...
Страница 108: ...Appendix F Wiring Diagram with Terminals Wiring diagram with a DPST disconnect switch 108 895 00677 Agri Alert 128 Touch...
Страница 109: ...Appendix F Wiring Diagram with Terminals Wiring diagram with a SPST disconnect switch 895 00677 Agri Alert 128 Touch 109...
Страница 110: ...NOTES 110 895 00677 Agri Alert 128 Touch...
Страница 118: ......