7.8 External fault indication
The pump incorporates a signal output for a
potential-free fault signal via terminals 7 and 8.
Functions of signal output
The fault signal output is activated when the pump
registers a fault. The fault signal relay is activated
together with the red indicator light on the pump.
Resetting of fault indications
A fault indication can be reset in one of the following
ways:
•
Briefly press or on the pump. This will not
influence the pump performance set.
•
Briefly switch off the power supply to the pump.
•
With the R100. See section
The fault indication cannot be reset until the cause of
the fault has disappeared.
7.9 External analog 0-10 V controller
The pump has an input for an external 0-10 VDC
analog signal transmitter (terminals 5 and 6). Via this
input, the pump can be controlled by an external
controller if the pump has been set to this control
mode:
•
Constant curve.
The external analog signal will set the pump
curve within the range from the min. curve to the
constant curve selected according to the
characteristic in fig. 13.
At an input voltage lower than 0.5 V, the pump will
operate according to the min. curve. The setpoint
cannot be changed.
The setpoint can only be changed when the input
voltage is higher than 0.5 V.
Fig. 13
Constant curve
Signal
output
Description
The power supply has been
switched off.
The pump is operating.
The pump has been set to stop.
The pump has stopped due to a
fault. Restarting will be attempted.
It may be necessary to restart the
pump manually by resetting the
fault indication.
The pump is operating, but it has
been stopped due to a fault.
Note:
If there is no differential-
pressure or temperature sensor
signal, the pump will continue
operating according to the max.
curve.
The pump has been set to stop, but
it has been stopped due to a fault.
7
8
7
8
7
8
7
8
7
8
7
8
TM
03
16
48
25
05
Pos.
Description
1
Maximum head/constant curve
2
Head set/constant curve
Note
The min. curve input, terminals 3 and 4,
must be short-circuited.
8
9
10
7
6
5
4
3
2
1
m
V
H
U
0
Min. curve
1
2
Содержание UPE 100-120 F
Страница 2: ......