background image

14

English (US)

7. Fault finding the product

DANGER

Electric shock

Death or serious personal injury
- Switch off the power supply before 

starting any work on the product. 
Make sure that the power supply 
cannot be accidentally switched on.

- Be aware that capacitors will be 

live up to 30 seconds after the 
power supply has been switched 
off.

Before dismantling the circulator, 
drain the system, or close the 
isolating valves on either side of the 
circulator.

CAUTION

Hot liquid

Minor or moderate personal injury
- The pumped liquid may be scalding 

hot.

CAUTION

Pressurized system

Minor or moderate personal injury
- The pumped liquid may be under 

high pressure.

Fault

Power supply

Cause

Remedy

1.

The pump does 

not run.

No power supply.

a)

The system is 

switched off.

Check the system 

controller.

b)

One fuse in the 

installation is 

blown.

Replace the fuse.

c)

The current-

operated or 

voltage-operated 

circuit breaker has 

tripped.

Cut in the circuit 

breaker.

d)

Power supply 

failure.

Check that the power 

supply falls within the 

specified range.

Normal power supply.

a)

The controller has 

switched off.

Check the controller 

and its settings.

b)

The pump is 

blocked by 

impurities.

Remove the impurities.

c)

The pump is 

defective.

Replace the pump.

2.

The pump cannot 

be controlled and 

only runs at 

maximum speed.

Normal power supply.

a)

No signal through 

the signal cable.

Check if the cable is 

connected to the 

controller. If yes, 

replace the cable.

3.

Noise in the 

system.

Normal power supply.

a)

Air in the system.

Vent the system.

b)

The outlet 

pressure is too 

high.

Reduce the setting of 

the controller or the 

valve.

4.

Noise in the pump. Normal power supply.

a)

Air in the pump.

Let the pump run. The 

pump vents itself over 

time.

b)

The inlet pressure 

is too low.

Increase the inlet 

pressure or check the 

air volume in the 

expansion tank, if 

installed.

5.

Insufficient flow.

Normal power supply.

a)

The pump 

performance is too 

low.

Check the controller 

and its settings.

b)

The hydraulic 

system is closed 

or the system 

pressure is 

insufficient.

Check the check valve 

and filter. Increase the 

system pressure.

Содержание TM07 2122 2818

Страница 1: ...GRUNDFOS INSTRUCTIONS ALPHA 26 99 Installation and operating instructions...

Страница 2: ...service under this warranty the defective product must be returned to the distributor or dealer of Grundfos products from which it was purchased together with proof of purchase and installation date f...

Страница 3: ...ates a hazardous situation which if not avoided will result in death or serious personal injury WARNING Indicates a hazardous situation which if not avoided could result in death or serious personal i...

Страница 4: ...s Fig 1 Control box positions DANGER Electric shock Death or serious personal injury Switch off the power supply before starting any work on the product Make sure that the power supply cannot be accid...

Страница 5: ...al of the relay is able to handle higher inrush currents We recommend to use special inrush relays with silver tin oxide AgSnO contacts Leakage current The pump mains filter causes a leakage current t...

Страница 6: ...injury Switch off the power supply before starting any work on the product Make sure that the power supply cannot be accidentally switched on WARNING Electric shock Death or serious personal injury Th...

Страница 7: ...must be connected to an external main switch with a minimum contact gap of 0 12 inches 3 mm in all poles Grounding or neutralization must be used for protection against indirect contact WARNING Electr...

Страница 8: ...Technical data The pump is suitable for the following liquids Clean thin non aggressive and non explosive liquids without solid particles or fibers If the pump is installed in a heating system the wa...

Страница 9: ...Voltage V 3 Frequency Hz 4 Approval mark UL 5 Input power P1 W at maximum and minimum performance 6 Rated current A at maximum and minimum performance 7 Speed 8 Enclosure class 9 Product number 10 Pr...

Страница 10: ...0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 Q m h 0 0 0 5 1 0 0 5 2 0 2 5 3 0 3 5 4 0 4 5 5 0 5 5 6 0 6 5 7 0 Proportional pressure 3 Proportional pressure 2 Proportional pressure 1 Proportional pressure...

Страница 11: ...10 VDC ALPHA1 26 99 circulators are externally speed controlled by an analog 0 10 V DC signal The pump requires a 0 10 V signal on the signal port to control the speed of the pump The pump will run at...

Страница 12: ...d as cable break Rating Value Rated input voltage high level UIH 4 24 V Rated input voltage low level UIL 1 V High level input current IIH 10 mA PWM frequency output open collector f 75 Hz 5 Accuracy...

Страница 13: ...as already been selected Start at the actual setting Press the button for two seconds The pump enters setting mode and the LED starts flashing Each time you press the button the setting changes LEDs 1...

Страница 14: ...uit breaker d Power supply failure Check that the power supply falls within the specified range Normal power supply a The controller has switched off Check the controller and its settings b The pump i...

Страница 15: ...r the pump surface Storage temperature Maximum 158 F 70 C Liquid temperature Maximum continuously 203 F 95 C Minimum 14 F 10 C Inrush current Measured on a flicker network according to IEC 61000 3 3 1...

Страница 16: ...16...

Страница 17: ...0 www grundfos us GRUNDFOS Canada 2941 Brighton Road Oakville Ontario L6H 6C9 Canada Phone 1 905 829 9533 Telefax 1 905 829 9512 www grundfos ca GRUNDFOS M xico Boulevard TLC No 15 Parque Industrial S...

Страница 18: ...com Trademarks displayed in this material including but not limited to Grundfos the Grundfos logo and be think innovate are registered trademarks owned by The Grundfos Group All rights reserved 2020 G...

Отзывы: